Installing the Inverter
975-0411-01-01
2–15
This guide for use by qualified installers only
7. Strip about 2 inches (50 mm) from the jacket of the AC output cable.
8. Strip approximately 3/8 inch (10 mm) off the insulation of each
conductor.
9. Run the AC output cable through the strain-relief clamp.
10. Using a 1/8 inch slot screwdriver, loosen the wire attachment screws on
the terminals.
11. Insert the ground (bare or green) wire into the Ground ("G") terminal.
12. Insert the Line (black) and Neutral (white) wires into the Line ("L") and
Neutral ("N") terminals respectively.
13. Tighten the wire terminal screws to a torque of 1.3–1.8 ft-lbs
(1.76–2.44 Nm).
14. Leaving some slack in the cable inside the wiring compartment, secure
the strain-relief clamp.
NOTE: Make sure that you are clamping the cable’s jacket and not the
individual insulated conductors.
15. Connect the outgoing AC wires to the AC load panel.
Figure 2-7
AC Wiring Compartment
AC knockout
AC
terminal
block
AC output terminals:
Ground
Neutral
Line
AC cover
AC knockout with
strain-relief clamp