Features and Specifications
Specifications
20
Operating Manual for XKW 1kW Series Power Supply
Remote
Programming
and
Monitoring
Environmental
Specification
Remote Start/Stop and Interlock
TTL compatible input. Contact Closure,
12-250 Vac or 12-130 Vdc
Remote Monitoring
0-5 V
1
Remote Programming and
Monitoring Accuracy
Programming better than 5%
Monitoring voltage 10%
Current 5%
Maximum Remote Sense Line Drop
Compensation
1 V
2
1. The 0-5 V voltage monitor signal is uncalibrated while the 0-5 V current monitor is calibrated,
0 = 0% output, 5 V = 100% output.
2. 0.5 V on 8-125 model.
Operating Temperature Range
0-50 °C
Storage Temperature Range
-55 °C to +85 °C
Humidity Range
Up to 80% non-condensing
Operating Altitude
Derate maximum operating temperature by 1°C
per 1,000 feet (300 m) for operation between
5,000 feet and (1,500 m) and 15,000 feet
(4,500 m)
Storage Altitude
Up to 50,000 feet (15,000 m)
Installation Category
II
Pollution Degree
2
Содержание XKW 150-7