Operating Instructions
TM-DIOP-01XN-01
4-19
Automatic Shutdown Email
When the inverter shuts down due to a fault or a user shutdown, the
Ethernet interface will attempt to send an email to the configured “Email
Alert Address” using the configured “SMTP Server” (see “Network
Connection” on page 4–9).
Contents of the email:
From: XDI <serial number>
To: <Email Alert Address>
Subject: Unit has shutdown
Body:
Serial # <Serial> at <IP> has shutdown. <Shutdown_Code>
The shutdown code list is a list of decimal values that represent specific
shutdown conditions (Table 4-7, “Shutdown Code” on page 4–19)
currently exhibited by the inverter. Each shutdown code is separated by a
space.
Important:
By the time you have received the email, if the inverter has
shutdown due to a fault, the inverter may have already corrected the problem.
Table 4-7
Shutdown Code
Code
Fault Description
16
Reserved
15
Reserved
14
Reserved
13
Input stage voltage out of range
12
DC link stage over voltage
11
Output stage over voltage
10
Multiple output stage over current
9
Output overload
8
Synchronization error
7
Over temperature
6
Output disabled via interlock
5
Output disabled via interface command
4
Output disabled by user.
(To enable, toggle interlock or interface command)
3
DC link stage under voltage
2
Output stage under voltage
1
Output stage over current
Содержание XDI2048
Страница 1: ...Operating Manual Xantrex Datacom Inverter XDI2048 2kVA 1 5kW ...
Страница 2: ......
Страница 3: ...Xantrex Datacom Inverter XDI2048 2kVA 1 5kW Operating Manual ...
Страница 8: ...vi ...
Страница 14: ...xii ...
Страница 16: ...xiv ...
Страница 42: ...2 22 ...
Страница 79: ...A Specifications Appendix A supplies information about specifications for the XDI Inverter and the Ethernet ...
Страница 86: ...A 8 ...
Страница 91: ......