Rack Mount Frame Assembly and Installation
2-8
TM-DIOP-01XN-01
4. Note the polarity on the input connector as indicated and fasten the
positive and negative cable ends onto the terminal block using the
brass screws and washers provided. Tighten both securely. See Figure
2-6.
5. The DC input wiring should be appropriately restrained to the
equipment rack to provide strain relief.
WARNING
Appropriate care and attention must be exercised when connecting any
equipment to a DC supply system due to the short circuit energy hazard that
exists.
WARNING
It is critical that the wires be stripped the right length so that the insulator enters
the connector.
WARNING
To avoid the risk of a short-circuit hazard, bare wire must NOT protrude past the
connector.
Figure 2-6
Connecting the Input Wires
DC Input