3-Phase, 4-Wire Y-Connection Output Wiring
This scheme is the same as the preceding with the addition of a neutral
connection.
•
All outputs should be wired through an appropriately rated circuit
breaker.
•
Connect L2 terminals of the three phases to the neutral bus.
•
Connect L1 of phase-1 to Line-1 output.
•
Connect L1 of phase-2 to Line-2 output.
•
Connect L1 of phase-3 to Line-3 output.
Ethernet
Port
Network connection to each inverter module is made through a standard
RJ-45 connector mounted on the rack mount frame assembly.