Rack Mount Frame Assembly and Installation
2-20
TM-DIOP-01XN-01
3-Phase, 3-Wire Delta Output Wiring
•
All outputs should be wired through an appropriately rated circuit
breaker.
•
On Phase-1, Connect terminal L1 to phase-3 Terminal L2.
•
On phase-1, connect terminal L2 to phase-2 terminal L1.
•
On phase-2, connect terminal L2 to phase-3 terminal L1.
3-Phase, 3-Wire Y-Connection Output Wiring
•
All outputs should be wired through an appropriately rated circuit
breaker.
•
Connect L2 terminals of the three phases to a common bus.
•
Wire L1 of phase-1 to Line-1 output.
•
Wire L1 of phase-2 to Line-2 output.
•
Wire L1 of phase-3 to Line-3 output.
L1
L2
L2
L1
L1
L2
L1
L2
L2
L1
L1
L2