The items listed in this addendum have changed to reflect product compliance with UL1741 First

Edition requirements. The changes only affect 120 VAC/60 Hz units using the SELL mode function

of the inverter/charger. The software revision has changed from 4.01 to 4.10.

Model Numbers Affected:

SW4024, SW4048 and SW5548 (120 VAC/60 Hz models only)

General Information:

The inverter software has been redesigned to meet UL1741 First Edition requirements which

incorporates IEEE929 recommended practices. These requirements have altered voltage and

frequency operating windows and have added a 5 minute grid connect timer delay before selling

power. In addition to user utility interactive changes, the inverter has been approved to meet the

rigorous non-islanding and harmonics analyses initiated by UL1741.

The SELL voltage window is now nonadjustable and locked at 106–132 VAC range, indicated by

the inverter’s LINE TIE LED ON. Any voltage limits programmed in 

SET INPUT LOWER/UPPER

LIMIT VAC

 menu item (located under 

MENU HEADING 11

) for input AC1, are displayed, but ignored

when the SELL mode is selected.

The SELL frequency window is nonadjustable and locked at 59.3–60.5 Hz anytime the inverter

is in SELL mode. This is indicated by the LINE TIE LED ON. For any voltage or frequency condition

outside these specified operating windows, the inverter will disconnect and attempt to reconnect to

the grid when proper voltage and frequency conditions are detected (after a 5 minute wait period

elapses). The inverter will reset the 5 minute timer each time an out-of-bounds condition is detected,

during periods when the AC1 light is blinking or ON.

SOFTWARE REV 4.10

SW4024

SW4048

SW5548

AC Voltage Window

Fixed 106–132 VAC when SELL mode is
engaged (AC1 input only). Adjustable for all
other modes.

Frequency Window

59.3–60.5 Hz in SELL mode (AC1 input only),
54–66 Hz for all other modes.

SET MAX SELL AMPS

1–35

1–35

1–50

Default 33 A

Default 33 A

Default 46 A

SET MAX CHARGE AMPS

1–35

1–35

1–40

Default 30 A

Default 30 A

Default 35 A

TRACE ENGINEERING 3
Menu

REV 4.10

976-0013-D-001

1

ADDENDUM

Содержание PLUS SW4024

Страница 1: ... 2000 Xantrex Technology Inc Addendum to the Installation and Operator s Manual for SW4024 SW4048 SW5548 Models Only SW Series ã2000 Xantrex 976 0013 01 01 Rev A 11 00 TM ...

Страница 2: ... 2000 Xantrex Technology Inc ...

Страница 3: ...y voltage limits programmed in SET INPUT LOWER UPPER LIMIT VAC menu item located under MENU HEADING 11 for input AC1 are displayed but ignored when the SELL mode is selected The SELL frequency window is nonadjustable and locked at 59 3 60 5 Hz anytime the inverter is in SELL mode This is indicated by the LINE TIE LED ON For any voltage or frequency condition outside these specified operating windo...

Страница 4: ...VAC OPERATING FREQUENCY RANGE 54 66 HZ MAX CONTINUOUS BATTERY CHARGER AC CURRENT 30 AMPS AC MAX CONTINUOUS BATTERY CHARGER DC CURRENT 110 AMPS DC MAX CONTINUOUS BATTERY CHARGER INPUT VA 3600 VA TYPICAL BATTERY CHARGER POWER FACTOR 0 9 TO 1 0 MAX AC TRANSFER SWITCH INPUT CURRENT 60 AMPS AC UTILITY INTERACTIVE SYSTEM OPERATING AC INPUT VOLTAGE RANGE 106 132 VAC OPERATING FREQUENCY RANGE AC1 59 3 60 ...

Страница 5: ... inverter is between 88 to 110 of nominal AC line voltage Display Deletions The following menu display items have been deleted for various reasons unrelated to UL requirements Under the ERROR CAUSES 5 menu heading menu item INVERTER BREAKER TRIPPED has been deleted Under the GENERATOR MODE 2 menu heading menu item GEN MAX RUN TIME ERROR has been deleted Under the GENERATOR MODE 2 menu heading all ...

Страница 6: ... to island conditions As a result active control techniques have been incorporated into the SW inverter for detecting potential dispersed generation islands A utility wishing to ensure against renewable energy supported dispersed generation islanding may require the use of a non islanding inverter Trace has designed the new software protection system to comply with the requirements of the non isla...

Страница 7: ... 2000 Xantrex Technology Inc ...

Страница 8: ...visit our website at www traceengineering com 5916 195th Street N E Arlington WA 98223 Phone 360 435 8826 Fax 360 435 2229 ...

Отзывы: