©2000 Xantrex Technology Inc.

Over/Under Voltage Fluctuations

*“Trip time” refers to the time between the abnormal conditions being applied and the inverter

ceasing to energize the utility line.

Over/Under Frequency Disturbances

Small renewable energy systems are allowed to sell within a fixed frequency range of -0.7 Hz/

+0.5 Hz of the nominal frequency in which they will operate. When the utility frequency is outside the

range of the nominal frequency window, the inverter must cease to energize the utility line within 6

cycles.

Reconnect Delay After a Utility Disturbance

An unacceptable utility event causes the renewable energy system to disconnect from the utility

line. It will remain disabled until acceptable voltage and frequency have been maintained for a

minimum of five minutes. After the 5 minute timer is complete, the inverter is allowed to

automatically reconnect the renewable energy system to the utility.

Islanding Protection

The non-islanding inverter protection features required by UL1741 ensures that the inverter

ceases to energize the utility line when the inverter is subjected to island conditions. As a result,

active control techniques have been incorporated into the SW inverter for detecting potential

dispersed-generation islands.

A utility wishing to ensure against renewable-energy supported dispersed-generation islanding

may require the use of a non-islanding inverter. Trace™ has designed the new software protection

system to comply with the requirements of the non-islanding inverter section of UL1741.

Over-current Protection

The Trace™ SW Series inverters also include over-current protection for the inverter system.

This protective system is used if the inverter attempts to power too large of a load or if the inverter

loses synchronization with the utility grid.  This protective system is implemented with redundant

systems in analog hardware, microprocessor software and with a mechanical device (circuit

breaker).  This insures the inverter is protected from damage and can not create an unsafe fault

condition to the utility or residence.

VOLTAGE

MAXIMUM TRIP TIME*

Voltage < 60 V (< 50%)

6 cycles

Voltages between 60–106 V (50–88%)

120 cycles

Voltages between 106–132 V (88–110%)

Normal operation

Voltages between 132–165 V (110–137%)

120 cycles

Voltage >165 V (137%)

2 cycles

FREQUENCY

MAXIMUM TRIP TIME*

Frequency < 59.3 Hz

6 cycles

Frequency > 60.5 Hz

6 cycles

976-0013-D-002

ADDENDUM

4

Содержание PLUS SW4024

Страница 1: ... 2000 Xantrex Technology Inc Addendum to the Installation and Operator s Manual for SW4024 SW4048 SW5548 Models Only SW Series ã2000 Xantrex 976 0013 01 01 Rev A 11 00 TM ...

Страница 2: ... 2000 Xantrex Technology Inc ...

Страница 3: ...y voltage limits programmed in SET INPUT LOWER UPPER LIMIT VAC menu item located under MENU HEADING 11 for input AC1 are displayed but ignored when the SELL mode is selected The SELL frequency window is nonadjustable and locked at 59 3 60 5 Hz anytime the inverter is in SELL mode This is indicated by the LINE TIE LED ON For any voltage or frequency condition outside these specified operating windo...

Страница 4: ...VAC OPERATING FREQUENCY RANGE 54 66 HZ MAX CONTINUOUS BATTERY CHARGER AC CURRENT 30 AMPS AC MAX CONTINUOUS BATTERY CHARGER DC CURRENT 110 AMPS DC MAX CONTINUOUS BATTERY CHARGER INPUT VA 3600 VA TYPICAL BATTERY CHARGER POWER FACTOR 0 9 TO 1 0 MAX AC TRANSFER SWITCH INPUT CURRENT 60 AMPS AC UTILITY INTERACTIVE SYSTEM OPERATING AC INPUT VOLTAGE RANGE 106 132 VAC OPERATING FREQUENCY RANGE AC1 59 3 60 ...

Страница 5: ... inverter is between 88 to 110 of nominal AC line voltage Display Deletions The following menu display items have been deleted for various reasons unrelated to UL requirements Under the ERROR CAUSES 5 menu heading menu item INVERTER BREAKER TRIPPED has been deleted Under the GENERATOR MODE 2 menu heading menu item GEN MAX RUN TIME ERROR has been deleted Under the GENERATOR MODE 2 menu heading all ...

Страница 6: ... to island conditions As a result active control techniques have been incorporated into the SW inverter for detecting potential dispersed generation islands A utility wishing to ensure against renewable energy supported dispersed generation islanding may require the use of a non islanding inverter Trace has designed the new software protection system to comply with the requirements of the non isla...

Страница 7: ... 2000 Xantrex Technology Inc ...

Страница 8: ...visit our website at www traceengineering com 5916 195th Street N E Arlington WA 98223 Phone 360 435 8826 Fax 360 435 2229 ...

Отзывы: