©2000 Xantrex Technology Inc.

Menu Maps

The USER and SETUP menu have been updated to reflect the new software revision as follows:

Page 34–USER MENU. The software revision shown under menu heading 

“TRACE

ENGINEERING 3”

, menu item

 “REVISION 4.01”

 is changed to 

“

REVISION 4.10

An information file has been added to menu heading 11 and reads: “

IN SELL MODE AC1

INPUT VAC LIMITS FIXED AT 88% AND 110% OF NOMINAL

Menu System

Page 39–

“TRACE ENGINEERING (3)”

 menu heading. The software revision has been updated

from 

“4.01”

 to 

“4.10

Page 48–The 

“SET MAX CHARGE AMPS AC”

 menu item, the range has been changed from

“01 to 35 amps”

 to 

“

01 to 40 amps

”

 for the SW5548 model.

Page 54–

“BATTERY SELLING (17)”

 menu heading. The 

“SET MAX SELL AMPS AC”

 range has

been changed from 

“01 to 35 amps”

 to 

“

01 to 50 amps

”

 for SW5548 model.

Operation

Page 61– The following paragraph should be added to the UTILITY INTER-ACTIVE MODE

bulleted item: “

To meet agency approvals, SELL mode will sell power only between the locked

106–132 volts AC range and 59.3–60.5 Hz range windows (120 VAC/60 Hz models only).

”

Page 83–When in SELL mode, the 

SET INPUT LOWER LIMIT VAC

 is locked at 106 VAC and

sells power only when the AC output of the inverter is between 88 to 110% of nominal AC line

voltage.

Display Deletions

The following menu display items have been deleted for various reasons unrelated to UL

requirements.

Under the 

“ERROR CAUSES 5” 

menu heading, menu item 

“

INVERTER BREAKER TRIPPED

”

has been deleted.

Under the 

“GENERATOR MODE 2”

 menu heading, menu item 

“

GEN MAX RUN TIME ERROR

”

has been deleted.

Under the 

“GENERATOR MODE 2”

 menu heading, all references to the 

GEN MAX RUN TIMER

have been deleted (i.e., “

IF GEN RUNS FOR MORE THAN MAX RUN TIME THEN ERROR

”

).

Under 

“GEN AUTO START SETUP 12”

 menu heading, all references to the 

GEN MAX RUN

TIMER

 have been deleted (i.e., 

“

SET MAXIMUM RUN TIME H:M 08:00

” 

and

 “

SET MAX RUN TIME

TO 0 TO DEFEAT

”).

Utility Interactive Mode Islanding Protection Compliance

Trace™ SW inverters are capable of utility interactive operation, which includes utility protection

features to prevent injury and damage from occurring when power is sold to the utility grid.  These

protective systems utilize high-speed microprocessor hardware and software to detect the abnormal

conditions and disconnect the inverter from the utility grid.

The UL1741 standard requires specific responses by the inverter to abnormal voltage and

frequency conditions.  The following summarizes the voltage and frequency levels and the response

time period required, plus other features required by the UL1741 standard.

3

ADDENDUM

Содержание PLUS SW4024

Страница 1: ... 2000 Xantrex Technology Inc Addendum to the Installation and Operator s Manual for SW4024 SW4048 SW5548 Models Only SW Series ã2000 Xantrex 976 0013 01 01 Rev A 11 00 TM ...

Страница 2: ... 2000 Xantrex Technology Inc ...

Страница 3: ...y voltage limits programmed in SET INPUT LOWER UPPER LIMIT VAC menu item located under MENU HEADING 11 for input AC1 are displayed but ignored when the SELL mode is selected The SELL frequency window is nonadjustable and locked at 59 3 60 5 Hz anytime the inverter is in SELL mode This is indicated by the LINE TIE LED ON For any voltage or frequency condition outside these specified operating windo...

Страница 4: ...VAC OPERATING FREQUENCY RANGE 54 66 HZ MAX CONTINUOUS BATTERY CHARGER AC CURRENT 30 AMPS AC MAX CONTINUOUS BATTERY CHARGER DC CURRENT 110 AMPS DC MAX CONTINUOUS BATTERY CHARGER INPUT VA 3600 VA TYPICAL BATTERY CHARGER POWER FACTOR 0 9 TO 1 0 MAX AC TRANSFER SWITCH INPUT CURRENT 60 AMPS AC UTILITY INTERACTIVE SYSTEM OPERATING AC INPUT VOLTAGE RANGE 106 132 VAC OPERATING FREQUENCY RANGE AC1 59 3 60 ...

Страница 5: ... inverter is between 88 to 110 of nominal AC line voltage Display Deletions The following menu display items have been deleted for various reasons unrelated to UL requirements Under the ERROR CAUSES 5 menu heading menu item INVERTER BREAKER TRIPPED has been deleted Under the GENERATOR MODE 2 menu heading menu item GEN MAX RUN TIME ERROR has been deleted Under the GENERATOR MODE 2 menu heading all ...

Страница 6: ... to island conditions As a result active control techniques have been incorporated into the SW inverter for detecting potential dispersed generation islands A utility wishing to ensure against renewable energy supported dispersed generation islanding may require the use of a non islanding inverter Trace has designed the new software protection system to comply with the requirements of the non isla...

Страница 7: ... 2000 Xantrex Technology Inc ...

Страница 8: ...visit our website at www traceengineering com 5916 195th Street N E Arlington WA 98223 Phone 360 435 8826 Fax 360 435 2229 ...

Отзывы: