Planning
2–6
153379
This manual for use by qualified installers only
Conduit Entry
For a typical GT100 installation, the recommended cable entry is from beneath the
enclosure. Figure 2-2 below shows the maximum allowable areas (shaded) and
locations in which electrical conduits should be located when cable entry is from
beneath the enclosure.When routing cable and conduit, some installations may
make it necessary to penetrate the enclosure from above ground. Figure 2-3 on
page 2–7 shows the maximum allowable areas (shaded) and locations in which
electrical conduits may penetrate the enclosure of the GT100.
Figure 2-2
Conduit Entries Beneath Enclosure, Bottom View
414 mm
(16.31 in)
57 mm
(2.23in)
427 mm
(16.81 in)
57 mm
(2.23in)
127 mm
(5.00in)
282 mm
(11.11in)
282 mm
(11.11in)
877 mm
(34.54 in)