System Specifications
153379
A–3
This manual for use by qualified installers only
Electrical Specifications
Table A-2 provides the AC and DC specifications for the GT100.
Regulatory Specifications
Table A-3 provides the regulatory specifications for the GT100.
Table A-2
Electrical Specifications
Specification
GT100-480-NG and
GT100-480-PG
GT100-208-NG and
GT100-208-PG
Nominal AC Input Voltage
(+10% to -12% acceptable range)
480 Vac
(423 to 528 Vac)
208 Vac
(184 to 228 Vac)
Maximum Continuous AC Output Current
121 A
rms
278 A
rms
Nominal AC Input Frequency
(+0.5 to -0.7 Hz acceptable range)
60 Hz
(57.0 to 60.5 Hz)
60 Hz
(57.0 to 60.5 Hz)
Line Power Factor
>0.99
>0.99
Output Power
100 kW
100 kW
Sell Power Range
1 kW to 100 kW
1 kW to 100 kW
Peak Power Tracking Window
300 to 480 Vdc
300 to 480 Vdc
Maximum Open Circuit Voltage
600 Vdc
600 Vdc
Nominal DC Voltage
345 Vdc
345 Vdc
Maximum DC Current
347 A
347 A
DC Current Ripple
< 2% at rated power < 2% at rated power
Maximum Array Short Circuit Current
460 A
460 A
DC Back-feed Current
0 A
0 A
AC Current Distortion
< 5% THD at rated
power
< 5% THD at rated
power
Efficiency
> 96.0%
> 95.0%
Standby and Night-time Tare Loss
< 100 W
< 100 W
Table A-3
Regulatory Specifications
Standard
Regulation Met
General Standards
UL 1741 Rev 2005
UL 508C
IEEE 1547
CSA 107.1-01
Emitted Interference
IEEE Std C37.90.2-1995
FCC Class A
Содержание GT100 Series
Страница 1: ...Xantrex GT100 Grid Tied Photovoltaic Inverter Planning and Installation Manual ...
Страница 2: ......
Страница 8: ...vi ...
Страница 16: ...xiv ...
Страница 20: ...xviii ...
Страница 22: ...xx ...
Страница 24: ...xxii ...
Страница 66: ...3 16 ...
Страница 70: ...4 4 ...
Страница 77: ......