Warning Messages
975-0999-01-01
55
Event Code
Event Type
Condition
Mode
Action
E
- Escalating Auto Fault. See Action for more detail.
F
- Manual fault. Unit operation stops. See Action to remedy the condition and clear the Alert LED on the unit. See
Clear Faults and Warnings on page 41
.
W
- Warning. Unit operation continues.
W/F
- Unit operation continues with a warning until a manual fault is triggered. See Action to remedy the condition and clear the Alert LED on the unit. See
87
W
Fan fatigue warning
Any mode
If there is no issue with the fan/s, disconnect the unit from its DC and
AC power sources, then reconnect, and then restart the unit.
Perform
Step 8: Testing Your Installation
. If error detection
persists, contact customer service.
88
W
Fan fatigue warning
89
W
Fan lock warning
Any mode
If there is no issue with the fan/s, disconnect the unit from its DC and
AC power sources, then reconnect, and then restart the unit.
Perform
Step 8: Testing Your Installation
. If error detection
persists, contact customer service.
90
W
Fan lock warning
94
W
Remote Power Off
Any mode
No action required. The unit stops inverting or charging
immediately, and shuts down after five seconds. If the unit is
configured as a master, it signals other network devices to also shut
down.
95
W
Equalization Abort
Shore (AC) mode
Equalization terminated abnormally because of interrupted AC
input. Wait until AC input returns to in-tolerance condition.
96
W
Cannot Equalize
Shore (AC) mode
Change battery type if your batteries should be equalized. Gel or
AGM batteries should not be equalized. AC input is not qualified or
the charge setting is not adequate.
97
W
Battery Temperature Sensor
Shorted
Any mode
Replace battery temperature sensor.
Table 7 Event codes displayed on the LCD screen