Warning Messages
975-0999-01-01
53
Event Code
Event Type
Condition
Mode
Action
E
- Escalating Auto Fault. See Action for more detail.
F
- Manual fault. Unit operation stops. See Action to remedy the condition and clear the Alert LED on the unit. See
Clear Faults and Warnings on page 41
.
W
- Warning. Unit operation continues.
W/F
- Unit operation continues with a warning until a manual fault is triggered. See Action to remedy the condition and clear the Alert LED on the unit. See
66
F
System Configuration Fault
Multi-unit configuration
settings
Ensure each unit has a unique Device Number, and that
associations and physical connections have been configured
correctly.
67
F
Watchdog Error
Any mode
Clear faults/warnings and restart. If error persists, contact
customer service.
68
W/F
Tranformer Over
Temperature
Any mode
Reduce the loads connected to the AC outlet of the unit. Check that
the ventilation grille is not blocked. Check for ambient temperature
and move the unit to a cooler location whenever possible. Check
the fan for any obstruction and remove it.
69
F
External Sync Failed
Multi-unit configuration
Check connections and cable on external AC sync port. In a single-
inverter system, nothing must be plugged into the AC sync port.
Clear fault and try again. If these steps fail, the unit requires service.
71
F
Battery Discharge Over
Current
Inverter (Battery) mode
There is an excessive load on the Li-Ion battery. (The fault applies
only to Li-Ion batteries.) Change the default threshold of the max
battery discharge current limit or reduce the load.
72
F
External AC Contactor
Malfunction
Shore (AC) mode
Check why the AC contactor has failed. Check for fusing of coil,
wiring and connections. Verify that the AC contactor has power.
Table 7 Event codes displayed on the LCD screen