Adjusting Settings in Configuration Mode
38
Freedom EX 4000 Owner's Guide
Setting Name
Setting
Number
Default
Value
Range of Values
Unit Step
Description
Search Threshold
I4
50
25
to
255
W
5
Sets the inverter’s search sensitivity when
Search mode is enabled. When a load larger
than this setting is present, the inverter turns on.
Search Delay
I5
2
1
to
25
s
1
Sets the time between search pulses. When
searching for loads, the Freedom EX 4000
sends out search pulses to determine if a load
is present. If the Freedom EX 4000 finds a load
above the Search Threshold setting, the inverter
turns on.
Power Save
I6
DIS
(disable)
EnA
(enable)
DIS
(disable)
--
--
Enables or disables Power save mode. When
enabled, the Freedom EX 4000 reduces tare
loss from the battery by reducing the inverter
output from 120 volts to 108 volts when the
loads consume less than 100 watts.