3.0 OPERATION
52
©2000 Xantrex Technology Inc.
Charger Mode
(continued)
Figure 46
Equalize Positions on BATTERY TYPE SELECTOR Switch
Equalize 1
Equalize 2
Figure 48
Equalize 2 BATTERY CAPACITY Potentiometer (position 0)
Figure 47
Equalize 1 BATTERY CHARGER RATE Potentiometer (position 1)
Switch
Position
Description
12 Volt Models
24 Volt Models
Equalize
Float
Voltage
Bulk/Equalize*
Voltage
Float
Voltage
Bulk/Equalize*
Voltage
Charge
Rate
Time
0
Equalize 1
13.2
*15.0
26.4
*30.0
Battery
Capacity
Setting
(C/40)
6 hours minimum
12 hours maximum
1
Equalize 2
13.2
*15.5
26.4
*31.0
Battery
Charger
Rate Setting
(manual)
6 hours minimum
12 hours maximum
2
Deep Cell Lead Acid 2
13.3
15.0
26.6
30.0
3
Not Specified
13.6
14.3
27.2
28.6
4
Gel Cell 2
13.7
14.4
27.4
28.8
5
Gel Cell 1
13.5
14.1
27.0
28.2
6
PbCa–Lead Acid
13.2
14.3
26.4
28.6
7
Deep Cycle Lead Acid 1
(Default Setting)
13.4
14.6
26.6
29.2
8
NiCad 1
14.0
16.0
28.0
32.0
9
NiCad 2
14.5
16.0
29.0
32.0
NOTES:
Switch positions "0" and "1" are for monthly battery maintenance only. Return the switch to the appropriate position for the system’s batteries when
Equalize charging has completed. NEVER EQUALIZE SEALED BATTERIES! Use together with BATTERY CHARGER RATE potentiometer
(position 1) or BATTERY CAPACITY potentiometer (position 0).
Equalize voltages are displayed in the table with an asterisk (*)–switch positions "0" and "1" only.
Switch position "7" is the default value as shipped from the factory.
Always refer to the battery manufacturer's specifications for Float, Bulk and Equalize (if applicable) voltages.
975-0012-014