3.0 OPERATION
45
©2000 Xantrex Technology Inc.
Front Panel Controls and Indicators
(continued)
Battery Capacity
The Battery Capacity potentiometer is used to set the correct charge profile for the battery
capacity (amp-hours) used with the inverter (see illustration below). The setting allows the
inverter to calculate over-discharge protection values and also the end of the Bulk/Absorption
charge mode, at which point the inverter switches to the Float mode of battery charging.
The potentiometer should be adjusted as close as possible to the actual capacity of the
battery bank for optimum charging. If the systems battery bank is larger than 1000 amp-hours,
set the potentiometer for 1K.
NOTE: Most battery manufacturers list the amp/hour rating on the battery label.
Figure 41A
Battery Capacity Potentiometer
(New)
Figure 41B
Battery Capacity Potentiometer
(Old)
50 amp-hours
(small battery bank)
1000 amp-hours
(use for 1000 amp-hour
or larger battery banks)
125 amp-hours
250 amp-hours
370 amp-hours
500 amp-hours
50 amp-hours
(small battery bank)
1000 amp-hours
(use for 1000 amp-hour
or larger battery banks)
NOTE: The Battery Capacity (Amp/Hrs) potentiometer values have changed between the minimum
value of 50 Ah and 1 kAh. Please use the photo that matches your unit.