background image

44

Toolbox Menu

The Toolbox Menu logs all error codes from the VERSA and PIM, as well as other functions. Up to 15 error codes

can be logged. 

Table W:  Toolbox Menu

Outdoor Reset Concept

The Temperature controller can  change the System

Set  Point  based  on  outdoor  temperature  (Outdoor

Reset). The temperature controller varies the temper-

ature  of  the  circulating  heating  water  in  response  to

changes  in  the  outdoor  temperature.  The  heating

water  temperature  is  controlled  through  the  modula-

tion and/or sequencing of the cascade.

The Temperature controller can also control the sys-

tem  circulating  pump  with  an  adjustable  Outdoor

Cutoff.  When  the  outdoor  temperature  is  above  the

Outdoor Cutoff, the pump is turned off and no heating

water is circulated through the system. When the out-

door temperature drops below the Outdoor Cutoff, the

system pump relay is activated and the heating water

circulates through the system. The temperature of the

heating water is controlled by the Reset Ratio, Water

Offset, and changes with the outdoor temperature.

Reset Ratio/Outdoor Reset

When  a  building  is  being  heated,  heat  escapes

through  the  walls,  doors,  and  windows  to  the  colder

outside  air.  The  colder  the  outside  temperature,  the

more heat escapes. If you can input heat into the build-

ing at the same rate that it is lost out of the building,

then  the  building  temperatures  will  remain  constant.

The Reset Ratio is an adjustment that lets you achieve

this equilibrium between heat input and heat loss.

The  starting  point  for  most  systems  is  the  1.00

(OD):1.00  (SYS)  (Outdoor  Temperature:  Heating

Water Temperature)  ratio. This  means  that  for  every

degree the outdoor temperature drops, the tempera-

ture  of  the  heating  water  will  increase  one  degree.

With  the  VERSA,  both  ends  of  the  slope  are

adjustable.  It is factory set at 70

°

F water temperature

(Boil START) at 70

°

F outdoor air (OUT START), and

180

°

F water temperature (Boil DESIGN) at 10

°

F out-

door air (OUT DESIGN).

Each building has different heat loss characteristics. A

very well insulated building will not lose much heat to

the outside air, and may need a Reset Ratio of 2.00

(OD):1.00  (SYS)  (Outdoor:  Water).  This  means  the

outdoor temperature would have to drop 2 degrees to

increase the water temperature 1 degree. On the other

hand,  a  poorly  insulated  building  may  need  a  Reset

Ratio  of  1.00  (OD):2.00  (SYS).  This  means  that  for

each  degree  the  outdoor  temperature  dropped  the

water  temperature  will  increase  2  degrees.  The

VERSA control Reset Ratio allows for full customiza-

tion to match any buildings heat loss characteristics.

A heating curve that relies not only on Outdoor temper-

ature but also on the type of radiation will improve heat

comfort.  The  user  can  fine  tune  these  adjustments

based on the specific building need.

Item

Description

Lookup Active Error Look up and display the active error info.

USER TEST

Select ON to start the function.  The setting returns to default after the test is run.

(See Page 47 for details.)

MAX HEAT

Select ON to start the function.  The setting will time out to OFF after 24 hours or can

be set to OFF again by the user.  (See VERSA IC Applications Guide for details.)

P/N 104901

Software number of the Raypak VERSA

DEFAULTS

Resets to factory settings.  Press UP and DOWN for 1 second to show CLR and load

factory defaults to all settings.  This will also clear all history.

HISTORY

lookup logged error

Displayed when an error code is present.  1 indicates the most recent error code.

Press UP and DOWN for 1 second to clear the error logs.

Содержание 300A-850A

Страница 1: ...vapors and liquids or other combustible materials in the vicinity of this or any other appliance To do so may result in an explosion or fire WHAT TO DO IF YOU SMELL GAS Do not try to light any applia...

Страница 2: ...llowing Changes to pages 5 13 14 15 16 17 22 23 24 25 26 27 29 30 33 35 37 39 40 41 42 44 45 52 and 53 Additions Flushing Cleaning of System Piping and Cold Water Operation sections added starting on...

Страница 3: ...ing Connections 22 Venting 26 Venting Installation Tips 29 Venting Configurations 29 Condensate Management 34 Outdoor Installation 35 Controls 36 Operating Instructions 39 WIRING DIAGRAM 46 START UP 4...

Страница 4: ...CALIFORNIA PROPOSITION 65 This product contains chemicals known to the State of California to cause cancer birth defects or other reproductive harm WARNING Risk of electrical shock More than one disco...

Страница 5: ...k s standard war ranties Model Identification The model identification number and heater serial number are found on the heater rating plate located on the upper rear jacket panel The model number has...

Страница 6: ...ig 2 Component Locations Top Fig 3 Component Locations Rear Model No MBTUH Input Water conn NPT Gas conn NPT Vent Size inches Max Min N P Flue Intake 300A 300 60 1 1 2 3 4 3 4 4 4 400A 399 80 2 1 1 4...

Страница 7: ...water for use by individuals a thermostatically controlled mixing valve for reducing point of use water temperature is recommended to reduce the risk of scald injury Contact a licensed plumber or the...

Страница 8: ...ed parking garages must be located at least 18 in above the floor In addition the heater shall be installed such that the gas ignition system components are protected from water dripping spraying rain...

Страница 9: ...all local codes See Fig 5 Table F NOTE Use of this boiler in construction areas where fine particulate matter such as concrete or dry wall dust is present may result in damage to the boiler that is n...

Страница 10: ...ft 1 2m below or to side of opening 1 ft 30 cm above opening 3 ft 91 cm K Clearance to mechanical air supply inlet 3 ft 91 cm above if within 10 ft 3m horizontally 6 ft 1 83m L Clearance above paved...

Страница 11: ...to ducting combustion air to the unit the unit may be fully separated from room air by installing the TruSeal option This may be done either at the fac tory sales option D 21 or in the field sales op...

Страница 12: ...th the outdoors Canadian Installations opening s having a cross section area of not less than 1 in 2 per 7 000 BTUH 320 mm2 per kW up to and including 1 million BTUH plus 1 in 2 per 14 000 BTUH 160 mm...

Страница 13: ...auge pressure has been maintained throughout test 3 Check for leaks Repair if found Flushing Cleaning of System Piping Many of the chemicals used to perform this function will harm the heat exchanger...

Страница 14: ...rred method is an injection loop An injec tor pump approach has the added value of being able to adjust very quickly to changes in the system water coming back to the heater The integrated VERSA IC co...

Страница 15: ...D Hybrid sequencer sales option B 36 Proper place ment and method of installation are critical for proper operation of the system See Fig 7 The sensor must be installed in a drywell in conjunction wit...

Страница 16: ...y connected to a hot water storage tank For detailed information about applications and modes see VERSA IC manu al catalog 5000 72 Mode 1 Type H Units Only This mode selection is for hydronic heating...

Страница 17: ...ly sensor S6 and the Target Max setting when using the Indirect DHW sensor S5 The Boiler Pump 17 Fig 11 MODE 3 Single Boiler with Indirect on Boiler Loop Fig 12 WH Units Single Water Heater with Tank...

Страница 18: ...lieve test pressure in the gas supply line prior to re connecting the heater and its manual shut off valve to the gas supply line FAIL URE TO FOLLOW THIS PROCEDURE MAY DAMAGE THE GAS VALVE Over pressu...

Страница 19: ...s line pipe thread A pipe compound rated for use with natural and propane gases is recommended Apply sparingly only on male pipe ends leaving the two end threads bare CAUTION Support gas supply piping...

Страница 20: ...larger than hp or 5A must use a sepa rate power supply and run the power through an external field supplied pump contactor Use appropri ately sized wire as defined by NEC CSA and or local codes All p...

Страница 21: ...g 14 18 1 Verify that circuit breaker is properly sized by referring to heater rating plate A dedicated circuit breaker should be provided and sized for the heater and all pumps powered through the he...

Страница 22: ...LARM CONTROL SENSOR WIRING HIGH VOLTAGE POWER AND PUMP WIRING LOCATION RATING PLATE SUGGESTED ROUTING OF SENSOR CONTROL WIRING Fig 16 Rear Wiring Location Fig 18 XFyre Single Heater Control PLATFORM I...

Страница 23: ...ts to the PIM so it can activate the Indirect DHW pump and Boiler pump if needed If an optional Indirect DHW sensor is connected to J2 1 and J2 2 the PIM will pass this signal to the VERSA This allows...

Страница 24: ...does not create a short to ground Fig 20 XFyre Cascade System Wiring 24 Wiring the Cascade System Communication Bus 1 Designate the primary boiler as the master boiler boiler1 by leaving dip switch 2...

Страница 25: ...18 This connection must be pro vided through dry contacts closure NOTE This dry contacts closure can come from a room thermostat or a remote relay No power of any kind should be applied to either of...

Страница 26: ...ufacturer s installation instructions carefully Centrotherm polypropylene vent material is also approved to be used on XFyre products A vent adapter sales option D 33 must be used to ensure a proper s...

Страница 27: ...ions of the local building codes Support of Vent Stack The weight of the vent stack or chimney must not rest on the heater vent connection Support must be pro vided in compliance with applicable codes...

Страница 28: ...n The venting system must conform to local codes and or the current National Fuel Gas Code ANSI Z223 1 NFPA 54 The system setpoint must not exceed 180 F 28 damaging exterior finishes Use a 300 series...

Страница 29: ...s 300A 400A and 500A and 6 in 152mm for Models 700A and 850A The connection from the appliance vent to the stack must be as direct as possible and shall be the same di ameter as the vent outlet The ho...

Страница 30: ...serving any other appliances shall not be connected into any portion of mechanical draft systems operating under a positive pressure If an XFyre is installed to replace an exist ing unit the vent sys...

Страница 31: ...hrough the Wall Venting Refer to Table F and local codes Fig 28 Horizontal Through the Wall Direct Venting Refer to Table F and local codes a Seal any unused openings in the common venting system b Vi...

Страница 32: ...s not considered in the overall length of the venting system The vent must be installed to prevent flue gas leakage Care must be taken during assembly to ensure that all joints are sealed properly and...

Страница 33: ...the XFyre product Table Q Category IV Horizontal Vent Ducted Combustion Air CAUTION This venting system requires the installation of a condensate drain in the vent piping per the vent manufacturer s i...

Страница 34: ...d health of inhabitants TEST PORT FLUE VENT CONDENSATE TREATMENT CONDENSATE TRAP CONNECTION PVC PIPE 1 4 DROP PER FT VENT CONDENSATION TRAP FLOOR DRAIN OR SUMP PUMP 12 Fig 30 Guide for Condensate Pipi...

Страница 35: ...ent gas flue leaks Treatment systems should be checked at least once per year and the chips should be replenished as necessary When replacing the chips they should be no smaller than to avoid blockage...

Страница 36: ...out occurs To reset the lock out press and relase the RESET button located on the user interface Turning off the power to the heater WILL NOT reset the single try ignition module High Limit Manual Res...

Страница 37: ...t temperature of the unit during nor mal operation to prevent short cycling and nuisance trips 37 Flow Switch This standard dual purpose control shuts off the boil er in case of pump failure or low wa...

Страница 38: ...inside the switch housing Push the top of the plastic switch housing as shown in Fig 37 to reset a tripped pressure switch The LED will go out when the switch is reset Blocked Vent Switch The heater...

Страница 39: ...The user interface consists of several Menu options Press the MENU button to scroll through the different menus in the interface Press the ITEM button to scroll through available items within a select...

Страница 40: ...he blower heater cascade status pump operation and CFH information Some of the items displayed are mode specific and are only observable when its corre sponding mode is active Setup Menu To change set...

Страница 41: ...requires IND Sensor ON 6 F IND SUPPLY H MODE 2 3 OFF 50 F to PIM value Target boiler temperature for the DHW heat exchanger during indi rect DHW operation requires IND Sensor OFF 180 F DHW PRIORITY H...

Страница 42: ...been corrected and a 15 min waiting period has expired VENT WALL 22 F to 266 F N A Always model dependent Current Vent temperature LIMIT TEMP 22 F to 266 F N A Always Current Outlet Limit temperature...

Страница 43: ...o clear INLET HI All Records the highest boiler inlet temperature Press UP DOWN for 1 sec to clear INLET LO All Records the lowest boiler outlet temperature Press UP DOWN for 1 sec to clear DELTA T Al...

Страница 44: ...r temperature drops the tempera ture of the heating water will increase one degree With the VERSA both ends of the slope are adjustable It is factory set at 70 F water temperature Boil START at 70 F o...

Страница 45: ...leting heat loss calculations for the building Boiler Design Boil DESIGN The Boil DESIGN temperature is the water temperature required to heat the boiler zones when the outdoor air is as cold as the O...

Страница 46: ...46 WIRING DIAGRAM...

Страница 47: ...you cannot reach your gas supplier call the fire department Use only your hand to close the gas supply shut off valve outside the heater Never use tools If the knob will not turn by hand do not try to...

Страница 48: ...ield supplied on the 700A and 850A 4 Attach a 12 scale manometer to the downstream fitting on the gas manifold Measure point B in Fig 44 field supplied on the 700A and 850A 5 Attach a 12 scale manomet...

Страница 49: ...o the sight glass located at the bottom of the front panel to check igniter opera tion 3 The boiler ignites at 3000 RPM as indicated on the LCD display of the user interface 4 This boiler is equipped...

Страница 50: ...gnite after pre purge time delay 8 Check to see that the high limit control is set above the design temperature requirements of the system For multiple zones Check to make sure the flow is adjusted as...

Страница 51: ...inside front panel on boiler OPERATION Lighting Instructions 1 Before lighting make sure you have read all of the safety information in this manual 2 Set the thermostat to the lowest setting 3 Turn of...

Страница 52: ...ror Item Description and Troubleshooting OUTLET SEN Check the outlet water sensor and its wiring LIMIT SEN Check the high limit sensor and its wiring INLET SEN Check the inlet sensor and its wiring GA...

Страница 53: ...Fault Red LED 7 Flashes Check for proper water flow Check hi limit setting and outlet sensor Sensor Fault Red LED 8 Flashes See the VERSA IC Control for fault identification Check sensor and wiring N...

Страница 54: ...should be no resistance Fig 46 Direct Spark Igniter Water Sensor Outdoor Sensor Water Temperature F Resistance ohms 32 32550 41 25340 50 19870 59 15700 68 12490 77 10000 86 8059 95 6535 104 5330 113 4...

Страница 55: ...ensate drain is inspected and ensure that condensate is being directed to appropriate con densate management system or drain as required by local codes 3 Check that area is free from combustible mater...

Страница 56: ...nsor 4 Conduct a combustion test at high and low fire Carbon dioxide should be 8 5 to 9 0 at full fire for natural gas and between 9 5 to 10 0 for propane gas Carbon monoxide should be 150 ppm 5 Check...

Страница 57: ...to fol low the precautions listed for working with ceramic fibers 4 Spray the coils with clear water making sure to con fine the spray to the area being cleaned DO NOT get the back ceramic wall of th...

Страница 58: ...may however choose to use outside combustion air for one or more of these reasons 1 Installation is in an area containing contaminants listed below which will induce acidic condensation 2 You want to...

Страница 59: ...wall horizontally vented gas fueled equipment installed in every dwelling building or structure used in whole or in part for residential purposes including those owned or operated by the Commonwealth...

Страница 60: ...contamination of combustion air or use of chemical additives to water PARTS REPLACEMENT Under this Warranty Raypak will furnish a replacement for any failed part The failed part must first be returne...

Страница 61: ...e _____________ Stack Height _______ Low Water Cutoff _______________Test Category _________ sketch vent on reverse side Number of Tanks and Size Qty____ _______Gallons Vent Material _________________...

Страница 62: ...62...

Страница 63: ...63...

Страница 64: ...64 www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A...

Отзывы: