Optional
The Optional adjustable-setting manual-reset high
limit is located behind the front panel. To reset a high
limit lockout, press the reset button on the adjustable
manual reset limit as well as the reset button located
on the user interface.
High Limit — Auto Reset (Optional)
The heater may be equipped with a fixed auto-reset
high limit temperature device and/or an adjustable
auto-reset high limit temperature device. The optional
auto-reset high limit is located on the brass outlet
adapter inside the unit, and the adjustable auto-reset
high limit is located inside and behind the front panel.
CAUTION:
This appliance has provisions to be
connected to more than one supply source. To
reduce the risk of electric shock, disconnect all such
connections before servicing.
CAUTION:
Risk of electric shock: More than one
disconnect switch may be required to de-energize
the equipment before servicing.
Ignition Control Functions
When there is a call for heat, and all safeties are
closed, then the combustion air blower starts to purge
air from the combustion chamber. After the pre-purge,
the igniter is energized. The standard ignition module
will lock-out after failing to light 3 times during a call for
heat. To reset the lock-out, press and release the
RESET
button located on the user interface. The con-
trol will automatically reset after 1 hour. When in
lock-out the control will run the blower through a post-
purge cycle.
The single-try ignition module (part of the CSD-1
option) will attempt to light only one time before lock-
out occurs. To reset the lock-out, press and relase the
RESET
button located on the user interface.
Turning off the power to the heater WILL NOT reset
the single-try ignition module.
High Limit — Manual Reset
The heater is equipped with a fixed-setting manual-
reset high limit temperature device as standard and it
may have an additional optional adjustable manual-
reset high temperature device.
Standard
The fixed-setting manual-reset high limit is built into
the PIM, it utilizes a dual-element sensor located on
the outlet (see Fig. 32). To reset a high limit lock-out,
press and release the RESET button located on the
user interface.
STANDARD
LIMIT SENSOR
OPTIONAL
ADJUSTABLE
SETTING
Fig. 32: High Limit (Manual Reset)
NOTE:
Ignition modules are common for all model
sizes. However, model-specific operating parame-
ters are defined by their respective ID cards.
WARNING:
Turn off power to the boiler before
installing, adjusting or servicing any controls. Failure
to do so may result in board damage, malfunction,
property damage, personal injury, or death.
36
If the water temperature drops below 45˚F on the
Outlet or Inlet sensors, the Boiler pump is enabled.
The pump is turned off when both the Inlet and Outlet
temperatures rise above 50˚F.
If either the Outlet or Inlet temperature drops below
38°F, the VERSA starts the burner at the minimum fir-
ing rate. The burner cycle will terminate when both the
Inlet and Outlet temperatures rise above 42°F.
Controls
WARNING:
Installation, adjustment and service of
controls, including timing of various operating func-
tions, must be performed by a qualified installer,
service agency or the gas supplier. Failure to do so
may result in control damage, malfunction, property
damage, personal injury, or death.