Table T: Adjust Menu
Item
Application Range
Description
Default
TARGET
H MODE 1,2,3 RSET <> SETP
RSET = Outdoor Reset, SETP =Setpoint
SETP
TANK SETP
WH
OFF, 50
°
F to 150
°
F
Tank setpoint temperature
125
°
F
TANK DIFF
WH
2
°
F to 10
°
F
Tank Differential temperature
3
MODE
H MODE 1,2,3 1,2,3
Piping and application configuration
1
SETPOINT
H MODE 1,2,3 50
°
F to 220ºF
Boiler target temperature while a heat demand is present for set-
point operation
180
°
F
OUT START
H MODE 1,2,3 35
°
F to 85
°
F
Outdoor starting temperature - outdoor reset
70
°
F
OUT DESIGN
H MODE 1,2,3 -60
°
F to 45
°
F
Outdoor design temperature - outdoor reset
10
°
F
Boil START
H MODE 1,2,3 35
°
F to 150
°
F
Starting boiler target temperature when the outdoor temperature is
at outdoor start - outdoor reset
70
°
F
Boil DESIGN
H MODE 1,2,3 70
°
F to 200
°
F
Design boiler target temperature when the outdoor temperature is
at outdoor design - outdoor reset
180
°
F
TARGET MAX
H MODE 1,2,3 100
°
F to PIM value*
Maximum target system temperature
220
°
F
TARGET MIN
H MODE 1,2,3 OFF, 50
°
F to 190
°
F
Minimum target system temperature
50
°
F
TARGET DIFF
H MODE 1,2,3 2
°
F to 42
°
F
Differential for target system temperature
10
°
F
IND SENSOR
H MODE 1,2,3 OFF <> ON
Selects whether a DHW sensor is used for indirect DHW tank
OFF
IND SETP
H MODE 2,3
OFF, 50
°
F to 180
°
F
Target indirect DHW temperature (IND Sensor = ON, to enable
this setting)
140ºF
DHW DIFF
H MODE 2,3
2
°
F to 10
°
F
Differential for the target indirect DHW tank temperature, requires
IND Sensor = ON
6
°
F
IND SUPPLY
H MODE 2,3
OFF, 50
°
F to PIM value*
Target boiler temperature for the DHW heat exchanger during indi-
rect DHW operation, requires IND Sensor = OFF
180
°
F
DHW PRIORITY H MODE 2
OFF <> ON
Selects whether or not Indirect DHW priority is active during indi-
rect DHW operation
OFF
PRI OVR
H MODE 2,3
Au, 0:10hr to 2:00hr
Sets the length of the indirect DHW priority override time
1:00hr
SYS PURGE
All
OFF, 0:20min to 20:00min
Sets the length of the system pump purge
20 seconds
MIX TYPE
H/WH MIX
H (BOIL <> PLNT)
WH(1 <> 2)
Selects the type of control depending on pipe configuration for
CWP
H BOIL
WH 2
MIX TARGET
H/WH MIX
50ºF to 140ºF
Inlet target temperature
120ºF
MIX LOCK
H/WH MIX
ON <> OFF
The equipment will trigger a warning when “MIX Target” is not
reached within 7 minutes. MIX LOCK = ON, Alarm and lockout,
MIX LOCK = OFF; Alarm only
OFF
MIX TRIM
H/WH MIX
-5 to 5
This adjustment is for various types and sizes of units as well as
various actuator motor speeds and types supplied by Raypak
0
MIX SPEED
H/WH MIX
FAST <> MED <> SLOW
This setting defines speed of response
MED
MIX INV
H/WH MIX
ON <> OFF
This option is related to the use of spring return actuators with a
proportional valve
OFF
WWSD
H MODE 1,2,3 40
°
F to 100
°
F
The system warm weather shutdown temperature - outdoor reset,
requires TARGET = RSET
70
°
F
UNITS
All
deg F <> deg C
Show units using icons in display
deg F
MODBUS
All
OFF <> MNTR <>
TEMP <> RATE
ModBus Operating Mode: Off, Monitor, Temp Control, Rate
Control
OFF
ADDRESS
All
1 to 247
ModBus slave address
1
DATA TYPE
All
RTU <> ASCI
Modbus data type
RTU
BAUD RATE
All
2400 <> 9600 <> 19K2
<> 57K6 <> 115K
19K2
PARITY
All
NONE <> EVEN <> ODD
EVEN
41