background image

outdoors or spaces (crawl or attic) that freely com-

municate with the outdoors.

a. Where  directly  communicating  with  the  out-

doors  or  where  communicating  to  the

outdoors  through  vertical  ducts, 

each  open-

ing 

shall have a minimum free area of 1 in.

2

per  4,000  BTUH  (550  mm

2

per  kW)  of  total

input rating of all equipment in the enclosure.

b. Where  communicating  with  the  outdoors

through  horizontal  ducts,  each  opening  shall

have a minimum free area of 1 in.

2

per 2,000

BTUH (1,100 mm

2

per kW) of total input rat-

ing of all equipment in the enclosure.

2.

One permanent opening

, commencing within 12

in. (305 mm) of the top of the enclosure, shall be

permitted where the equipment has clearances of

at least 1 in. (25 mm) from the sides and back and

6 in. (152 mm) from the front of the appliance. The

opening shall directly communicate with the out-

doors or shall communicate through a vertical or

horizontal  duct  to  the  outdoors  or  spaces  that

freely  communicate  with  the  outdoors,  and  shall

have a minimum free area of:

a. 1 in.

2

per 3,000 BTUH (740 mm

2

per kW) of

the total input rating of all equipment located in

the enclosure, and

b. Not less than the sum of the areas of all vent

connectors in the confined space.

1. Ventilation  of  the  space  occupied  by  the  heater

shall be provided by an opening(s) for ventilation

air  at  the  highest  practical  point  communicating

with the outdoors. The total cross-sectional area of

such  an  opening(s)  shall  be  at  least  10%  of  the

area required in 2. and 3. (below), but in no case

shall the cross-sectional area be less than 10 in.

2

(65 cm

2

).

2. For heaters using a barometric damper in the vent

system,  there  shall  be  a  permanent  air  supply

12

WARNING: 

Do  not  use  the  “one  permanent

opening”  method  if  the  equipment  room  is  under

negative pressure conditions.

CAUTION:

All combustion air must be drawn from

the air outside of the building; the mechanical equip-

ment  room  must  communicate  directly  with  the

outdoors.

Canadian Installations

opening(s) having a cross section area of not less

than 1 in.

2

per 7,000 BTUH (320 mm

2

per kW) up

to  and  including  1  million  BTUH,  plus  1  in.

2

per

14,000  BTUH  (160  mm

2

per  kW)  in  excess  of  1

million  BTUH.  This  opening(s)  shall  be  either

located at or ducted to a point not more than 18 in.

(450 mm) nor less than 6 in. (152 mm) above the

floor level. The duct can also “goose neck” through

the roof. The duct is preferred to be straight down

and terminated 18 in. (450 mm) from the floor, but

not near piping. This air supply opening require-

ment  shall  be  in  addition  to  the  air  opening  for

ventilation air required in 1. (above).

3. For heaters when air supply is provided by natural

air  flow  from  outdoors  for  a  power  burner  and

there is no draft regulator, drafthood or similar flue

gas dilution device installed in the same space, in

addition to the opening for ventilation air required

in 1., there shall be a permanent air supply open-

ing(s) having a total cross-sectional area  of not

less than 1 in.

2

for each 30,000 BTUH (74 mm

2

per

kW) of total rated input of the burner(s), and the

location of the opening(s) shall not interfere with

the intended purpose of the opening(s) for ventila-

tion  air  referred  to  in  1.  This  opening(s)  can  be

ducted to a point not more than 18 in. (450 mm)

nor less than 6 in. (152 mm) above the floor level.

The duct can also “goose neck” through the roof.

The  duct  is  preferred  to  be  straight  down  18  in.

(450 mm) from the floor, but not near piping.

4. Refer to the B149 Installation Code for additional

information.

Water Piping

General

The heater should be located so that any water leaks

will not cause damage to the adjacent area or struc-

tures.

WARNING:

Care must be taken to ensure that the

equipment  room  is  not  under  negative  pressure

conditions.

NOTE:

Refer to the VERSA IC Applications Guide

(Catalog #5000.72) for detailed instructions regard-

ing  the  various  applications  supported  by  the

VERSA IC

®

control system.

WARNING:

Pump  motors  should  NOT  be

supported  by  any  type  of  stand  or  support  from

above  due  to  possible  misalignment  of  pump  and

motor which may occur.

Содержание 300A-850A

Страница 1: ...vapors and liquids or other combustible materials in the vicinity of this or any other appliance To do so may result in an explosion or fire WHAT TO DO IF YOU SMELL GAS Do not try to light any applia...

Страница 2: ...llowing Changes to pages 5 13 14 15 16 17 22 23 24 25 26 27 29 30 33 35 37 39 40 41 42 44 45 52 and 53 Additions Flushing Cleaning of System Piping and Cold Water Operation sections added starting on...

Страница 3: ...ing Connections 22 Venting 26 Venting Installation Tips 29 Venting Configurations 29 Condensate Management 34 Outdoor Installation 35 Controls 36 Operating Instructions 39 WIRING DIAGRAM 46 START UP 4...

Страница 4: ...CALIFORNIA PROPOSITION 65 This product contains chemicals known to the State of California to cause cancer birth defects or other reproductive harm WARNING Risk of electrical shock More than one disco...

Страница 5: ...k s standard war ranties Model Identification The model identification number and heater serial number are found on the heater rating plate located on the upper rear jacket panel The model number has...

Страница 6: ...ig 2 Component Locations Top Fig 3 Component Locations Rear Model No MBTUH Input Water conn NPT Gas conn NPT Vent Size inches Max Min N P Flue Intake 300A 300 60 1 1 2 3 4 3 4 4 4 400A 399 80 2 1 1 4...

Страница 7: ...water for use by individuals a thermostatically controlled mixing valve for reducing point of use water temperature is recommended to reduce the risk of scald injury Contact a licensed plumber or the...

Страница 8: ...ed parking garages must be located at least 18 in above the floor In addition the heater shall be installed such that the gas ignition system components are protected from water dripping spraying rain...

Страница 9: ...all local codes See Fig 5 Table F NOTE Use of this boiler in construction areas where fine particulate matter such as concrete or dry wall dust is present may result in damage to the boiler that is n...

Страница 10: ...ft 1 2m below or to side of opening 1 ft 30 cm above opening 3 ft 91 cm K Clearance to mechanical air supply inlet 3 ft 91 cm above if within 10 ft 3m horizontally 6 ft 1 83m L Clearance above paved...

Страница 11: ...to ducting combustion air to the unit the unit may be fully separated from room air by installing the TruSeal option This may be done either at the fac tory sales option D 21 or in the field sales op...

Страница 12: ...th the outdoors Canadian Installations opening s having a cross section area of not less than 1 in 2 per 7 000 BTUH 320 mm2 per kW up to and including 1 million BTUH plus 1 in 2 per 14 000 BTUH 160 mm...

Страница 13: ...auge pressure has been maintained throughout test 3 Check for leaks Repair if found Flushing Cleaning of System Piping Many of the chemicals used to perform this function will harm the heat exchanger...

Страница 14: ...rred method is an injection loop An injec tor pump approach has the added value of being able to adjust very quickly to changes in the system water coming back to the heater The integrated VERSA IC co...

Страница 15: ...D Hybrid sequencer sales option B 36 Proper place ment and method of installation are critical for proper operation of the system See Fig 7 The sensor must be installed in a drywell in conjunction wit...

Страница 16: ...y connected to a hot water storage tank For detailed information about applications and modes see VERSA IC manu al catalog 5000 72 Mode 1 Type H Units Only This mode selection is for hydronic heating...

Страница 17: ...ly sensor S6 and the Target Max setting when using the Indirect DHW sensor S5 The Boiler Pump 17 Fig 11 MODE 3 Single Boiler with Indirect on Boiler Loop Fig 12 WH Units Single Water Heater with Tank...

Страница 18: ...lieve test pressure in the gas supply line prior to re connecting the heater and its manual shut off valve to the gas supply line FAIL URE TO FOLLOW THIS PROCEDURE MAY DAMAGE THE GAS VALVE Over pressu...

Страница 19: ...s line pipe thread A pipe compound rated for use with natural and propane gases is recommended Apply sparingly only on male pipe ends leaving the two end threads bare CAUTION Support gas supply piping...

Страница 20: ...larger than hp or 5A must use a sepa rate power supply and run the power through an external field supplied pump contactor Use appropri ately sized wire as defined by NEC CSA and or local codes All p...

Страница 21: ...g 14 18 1 Verify that circuit breaker is properly sized by referring to heater rating plate A dedicated circuit breaker should be provided and sized for the heater and all pumps powered through the he...

Страница 22: ...LARM CONTROL SENSOR WIRING HIGH VOLTAGE POWER AND PUMP WIRING LOCATION RATING PLATE SUGGESTED ROUTING OF SENSOR CONTROL WIRING Fig 16 Rear Wiring Location Fig 18 XFyre Single Heater Control PLATFORM I...

Страница 23: ...ts to the PIM so it can activate the Indirect DHW pump and Boiler pump if needed If an optional Indirect DHW sensor is connected to J2 1 and J2 2 the PIM will pass this signal to the VERSA This allows...

Страница 24: ...does not create a short to ground Fig 20 XFyre Cascade System Wiring 24 Wiring the Cascade System Communication Bus 1 Designate the primary boiler as the master boiler boiler1 by leaving dip switch 2...

Страница 25: ...18 This connection must be pro vided through dry contacts closure NOTE This dry contacts closure can come from a room thermostat or a remote relay No power of any kind should be applied to either of...

Страница 26: ...ufacturer s installation instructions carefully Centrotherm polypropylene vent material is also approved to be used on XFyre products A vent adapter sales option D 33 must be used to ensure a proper s...

Страница 27: ...ions of the local building codes Support of Vent Stack The weight of the vent stack or chimney must not rest on the heater vent connection Support must be pro vided in compliance with applicable codes...

Страница 28: ...n The venting system must conform to local codes and or the current National Fuel Gas Code ANSI Z223 1 NFPA 54 The system setpoint must not exceed 180 F 28 damaging exterior finishes Use a 300 series...

Страница 29: ...s 300A 400A and 500A and 6 in 152mm for Models 700A and 850A The connection from the appliance vent to the stack must be as direct as possible and shall be the same di ameter as the vent outlet The ho...

Страница 30: ...serving any other appliances shall not be connected into any portion of mechanical draft systems operating under a positive pressure If an XFyre is installed to replace an exist ing unit the vent sys...

Страница 31: ...hrough the Wall Venting Refer to Table F and local codes Fig 28 Horizontal Through the Wall Direct Venting Refer to Table F and local codes a Seal any unused openings in the common venting system b Vi...

Страница 32: ...s not considered in the overall length of the venting system The vent must be installed to prevent flue gas leakage Care must be taken during assembly to ensure that all joints are sealed properly and...

Страница 33: ...the XFyre product Table Q Category IV Horizontal Vent Ducted Combustion Air CAUTION This venting system requires the installation of a condensate drain in the vent piping per the vent manufacturer s i...

Страница 34: ...d health of inhabitants TEST PORT FLUE VENT CONDENSATE TREATMENT CONDENSATE TRAP CONNECTION PVC PIPE 1 4 DROP PER FT VENT CONDENSATION TRAP FLOOR DRAIN OR SUMP PUMP 12 Fig 30 Guide for Condensate Pipi...

Страница 35: ...ent gas flue leaks Treatment systems should be checked at least once per year and the chips should be replenished as necessary When replacing the chips they should be no smaller than to avoid blockage...

Страница 36: ...out occurs To reset the lock out press and relase the RESET button located on the user interface Turning off the power to the heater WILL NOT reset the single try ignition module High Limit Manual Res...

Страница 37: ...t temperature of the unit during nor mal operation to prevent short cycling and nuisance trips 37 Flow Switch This standard dual purpose control shuts off the boil er in case of pump failure or low wa...

Страница 38: ...inside the switch housing Push the top of the plastic switch housing as shown in Fig 37 to reset a tripped pressure switch The LED will go out when the switch is reset Blocked Vent Switch The heater...

Страница 39: ...The user interface consists of several Menu options Press the MENU button to scroll through the different menus in the interface Press the ITEM button to scroll through available items within a select...

Страница 40: ...he blower heater cascade status pump operation and CFH information Some of the items displayed are mode specific and are only observable when its corre sponding mode is active Setup Menu To change set...

Страница 41: ...requires IND Sensor ON 6 F IND SUPPLY H MODE 2 3 OFF 50 F to PIM value Target boiler temperature for the DHW heat exchanger during indi rect DHW operation requires IND Sensor OFF 180 F DHW PRIORITY H...

Страница 42: ...been corrected and a 15 min waiting period has expired VENT WALL 22 F to 266 F N A Always model dependent Current Vent temperature LIMIT TEMP 22 F to 266 F N A Always Current Outlet Limit temperature...

Страница 43: ...o clear INLET HI All Records the highest boiler inlet temperature Press UP DOWN for 1 sec to clear INLET LO All Records the lowest boiler outlet temperature Press UP DOWN for 1 sec to clear DELTA T Al...

Страница 44: ...r temperature drops the tempera ture of the heating water will increase one degree With the VERSA both ends of the slope are adjustable It is factory set at 70 F water temperature Boil START at 70 F o...

Страница 45: ...leting heat loss calculations for the building Boiler Design Boil DESIGN The Boil DESIGN temperature is the water temperature required to heat the boiler zones when the outdoor air is as cold as the O...

Страница 46: ...46 WIRING DIAGRAM...

Страница 47: ...you cannot reach your gas supplier call the fire department Use only your hand to close the gas supply shut off valve outside the heater Never use tools If the knob will not turn by hand do not try to...

Страница 48: ...ield supplied on the 700A and 850A 4 Attach a 12 scale manometer to the downstream fitting on the gas manifold Measure point B in Fig 44 field supplied on the 700A and 850A 5 Attach a 12 scale manomet...

Страница 49: ...o the sight glass located at the bottom of the front panel to check igniter opera tion 3 The boiler ignites at 3000 RPM as indicated on the LCD display of the user interface 4 This boiler is equipped...

Страница 50: ...gnite after pre purge time delay 8 Check to see that the high limit control is set above the design temperature requirements of the system For multiple zones Check to make sure the flow is adjusted as...

Страница 51: ...inside front panel on boiler OPERATION Lighting Instructions 1 Before lighting make sure you have read all of the safety information in this manual 2 Set the thermostat to the lowest setting 3 Turn of...

Страница 52: ...ror Item Description and Troubleshooting OUTLET SEN Check the outlet water sensor and its wiring LIMIT SEN Check the high limit sensor and its wiring INLET SEN Check the inlet sensor and its wiring GA...

Страница 53: ...Fault Red LED 7 Flashes Check for proper water flow Check hi limit setting and outlet sensor Sensor Fault Red LED 8 Flashes See the VERSA IC Control for fault identification Check sensor and wiring N...

Страница 54: ...should be no resistance Fig 46 Direct Spark Igniter Water Sensor Outdoor Sensor Water Temperature F Resistance ohms 32 32550 41 25340 50 19870 59 15700 68 12490 77 10000 86 8059 95 6535 104 5330 113 4...

Страница 55: ...ensate drain is inspected and ensure that condensate is being directed to appropriate con densate management system or drain as required by local codes 3 Check that area is free from combustible mater...

Страница 56: ...nsor 4 Conduct a combustion test at high and low fire Carbon dioxide should be 8 5 to 9 0 at full fire for natural gas and between 9 5 to 10 0 for propane gas Carbon monoxide should be 150 ppm 5 Check...

Страница 57: ...to fol low the precautions listed for working with ceramic fibers 4 Spray the coils with clear water making sure to con fine the spray to the area being cleaned DO NOT get the back ceramic wall of th...

Страница 58: ...may however choose to use outside combustion air for one or more of these reasons 1 Installation is in an area containing contaminants listed below which will induce acidic condensation 2 You want to...

Страница 59: ...wall horizontally vented gas fueled equipment installed in every dwelling building or structure used in whole or in part for residential purposes including those owned or operated by the Commonwealth...

Страница 60: ...contamination of combustion air or use of chemical additives to water PARTS REPLACEMENT Under this Warranty Raypak will furnish a replacement for any failed part The failed part must first be returne...

Страница 61: ...e _____________ Stack Height _______ Low Water Cutoff _______________Test Category _________ sketch vent on reverse side Number of Tanks and Size Qty____ _______Gallons Vent Material _________________...

Страница 62: ...62...

Страница 63: ...63...

Страница 64: ...64 www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A...

Отзывы: