Manual 35086
ProTech-GII with Math Functions
Woodward
81
The following trip functions are always enabled / active:
Internal Fault Trip:
Indicates a failure internal to the ProTech-GII. Additional details on the fault
cause are provided in the PCT’s Module Faults Log.
Configuration Trip:
Indicates new configuration settings were loaded into the module or a trip was
issued from the front panel to enter configuration mode. Pressing the Reset button will clear the
error.
Parameter Error:
Indicates a parameter error was detected, meaning there was a problem reading
the settings out of the ProTech non-volatile memory during initial startup. The ProTech-GII remains
in a tripped state. The configuration must be re-loaded via the PCT and a power cycle is required to
clear this error.
The following trip functions are only active when configured for use:
Overspeed Trip:
Indicates an overspeed trip. Only provided when the Speed Redundancy Manager
or the Speed Input is configured for use.
Overaccel Trip:
Indicates an over-acceleration trip
Power Up Trip:
Indicates a power-up condition was detected. Only provided if the trip latch is
configured as “De-energize to Trip”.
Speed Redundancy Manager Trip:
Indicates the Speed Redundancy Manager caused a trip.
Speed Probe Open Wire:
Indicates a broken wire or faulty speed probe has been detected. Only
provided when configured for passive probe type and Speed Redundancy Manager is not
configured. If the Speed Redundancy Manager is configured, the Open Wire detection will be
indicated as a Speed Probe Open Wire Alarm instead of a Speed Probe Open Wire Trip.
Speed Lost Trip:
Indicates an instantaneous speed loss event. Only provided if the Speed Input is
configured for use. A Sudden Speed Loss event is detected when a speed of zero is sensed and,
during the previous four millisecond scan, a value above the “Speed Loss Threshold” (default 200.0
RPM) was sensed.
Speed Fail Trip:
Indicates speed was detected below the “Speed Fail Setpoint”. Only provided when
the Speed Redundancy Manager or the Speed Input is configured for use.
Speed Fail Timeout:
Indicates lack of speed detected during a start condition. Only provided when
the Speed Redundancy Manager or the Speed Input is configured for use.
Monitor Alarm Latch Page
Figure 4-10. Monitor Alarm Latch Screen Example
This page displays the status of each Alarm Latch input. All alarm conditions are latched and require a
reset command to clear the fault indication. The following alarms are always active and displayed if
sensed:
Internal Fault Alarm:
Indicates a failure internal to the ProTech-GII module. Additional details on the
fault cause are provided in the Module Faults Log, accessible via the PCT.
Released
Содержание ProTech-GII
Страница 60: ...Manual 35086 ProTech GII with Math Functions Woodward 58 Figure 3 8 Simplex Trip Block Assembly Released ...
Страница 189: ...Manual 35086 ProTech GII with Math Functions Woodward 187 Figure A 13 Advanced Menu Released ...
Страница 193: ...Manual 35086 ProTech GII with Math Functions Woodward 191 Revision History New Manual Released ...
Страница 194: ...Manual 35086 ProTech GII with Math Functions Woodward 192 Declarations Released ...