Manual 35086
ProTech-GII with Math Functions
Woodward
117
Figure 6-4. Test Frequency Resolution
Figure 6-5. Manual Simulated Speed Test Screen Example
The following Screen Messages may be seen on the Manual Simulated Speed Test page:
Manual Simulated Speed Active: This message indicates the Manual Simulated Speed Test is active.
Test Time Expired
: This message indicates the “Test Time Remaining” timer has reached zero before
the simulated speed level was raised above the Overspeed Trip setpoint.
Manual Simulated Speed Test Procedure
1. Verify no modules are in a Tripped or Alarmed state (depends on the configured Test Mode
Permissive setting).
2. From the “Manual Simulated Speed Test” screen, press the “Start Test” soft key.
3. The “Password Entry” screen will appear. Enter the Test Level Password.
4. Press the “Apply” soft key to initiate this test or press the “Cancel” soft key to exit the screen.
a. The local input speed channel is then switched from sensing actual rotating equipment speed
to sensing the module’s internal frequency generator, automatically set to a simulated speed
of 100 RPM below the local “Overspeed Trip” level setting.
0.00001
0.00010
0.00100
0.01000
0.10000
1.00000
10.00000
10.0
100.0
1000.0
10000.0
Resolution
(RPM)
RPM
Test
Frequency
Resoultion
#
Teeth
=
60
Gear
Ratio
=
1
Resolution
Released
Содержание ProTech-GII
Страница 60: ...Manual 35086 ProTech GII with Math Functions Woodward 58 Figure 3 8 Simplex Trip Block Assembly Released ...
Страница 189: ...Manual 35086 ProTech GII with Math Functions Woodward 187 Figure A 13 Advanced Menu Released ...
Страница 193: ...Manual 35086 ProTech GII with Math Functions Woodward 191 Revision History New Manual Released ...
Страница 194: ...Manual 35086 ProTech GII with Math Functions Woodward 192 Declarations Released ...