Manual 35086
ProTech-GII with Math Functions
Woodward
173
Problem or
Diagnostic Indication
Description
Possible Cause
Suggested Actions
Speed Probe Open
Wire Alarm
(if speed redundancy is
used)
The module has
detected an open wire
condition on the speed
probe (Passive or
MPU probe only)
Wiring fault or probe
fault.
Check wiring continuity and
probe integrity.
Speed RM Difference
(if speed redundancy is
used)
One of the speed
probes is reading
different from the
others.
Wiring fault, speed
probe fault.
Incorrect speed gear
ratio or number of teeth
configured,
Check wiring continuity and
probe integrity, replace
probe.
Check speed sensor
configuration.
Speed RM In 1 Invalid
(if speed redundancy is
used)
The Input 1 signal to
the speed redundancy
manager block is
failed –(may be from
other module).
Wiring fault or probe
fault.
Verify which module speed
input is connect to input #1,
then check wiring continuity
and probe integrity, replace
probe.
Speed RM In 2 Invalid
(if speed redundancy is
used)
The Input 2 signal to
the speed redundancy
manager block is
failed –(may be from
other module).
Wiring fault or probe
fault.
Verify which module speed
input is connect to input #2,
then check wiring continuity
and probe integrity, replace
probe.
Speed RM In 3 Invalid
(if speed redundancy is
used)
The Input 3 signal to
the speed redundancy
manager block is
failed –(may be from
other module).
Wiring fault or probe
fault.
Verify which module speed
input is connect to input #3,
then check wiring continuity
and probe integrity, replace
probe.
Tmp Overspd Setpoint
On
Indicates the
temporary overspeed
setpoint has been
activated.
User initiated temporary
setpoint test.
See manual for description
and limitations.
Use PCT or front panel to
verify settings.
Manual Sim Speed
Test
Indicates the manual
simulated overspeed
test has been
activated.
User initiated simulated
speed test.
See manual for description
and limitations.
Auto Sim Speed Test
Indicates the
automated simulated
overspeed test has
been activated.
User initiated simulated
speed test.
See manual for description
and limitations.
Auto Sim Spd Test
Failed
Indicates the
automated simulated
overspeed test failed.
Internal problem with the
unit.
Return unit to Woodward.
Auto Sequence Test
Indicates the
automated Auto
Sequence Test has
been activated.
User enabled the auto
sequence test or test
interval time expired and
test started.
See manual for description
and limitations.
Use PCT or module A front
panel to verify settings.
Released
Содержание ProTech-GII
Страница 60: ...Manual 35086 ProTech GII with Math Functions Woodward 58 Figure 3 8 Simplex Trip Block Assembly Released ...
Страница 189: ...Manual 35086 ProTech GII with Math Functions Woodward 187 Figure A 13 Advanced Menu Released ...
Страница 193: ...Manual 35086 ProTech GII with Math Functions Woodward 191 Revision History New Manual Released ...
Страница 194: ...Manual 35086 ProTech GII with Math Functions Woodward 192 Declarations Released ...