Gen.overload
D
Gen.-Überlast
Alarm message: Generator overload
Alarm class: 3
The limit values for monitoring the generator overload are exceeded for the period
of delay time.
GB
Revers/min.power
D
Rück/Minderleist
Alarm message: Generator reverse-/-reduced load Alarm class: 3
The limit values for monitoring the generator reverse-/-reduced load are under-
run/exceeded for the period of delay time.
GB
Load unbalanced
D
Schieflast
Alarm message: Load unbalance
Alarm class: 1
The limit values for monitoring the load unbalance are exceeded for the period of
delay time.
GB
Gen.overcurr. 1
D
Gen.-Überstrom 1
Alarm message: Generator overcurrent, limit value 1 Alarm class:
The limit values for monitoring the generator overcurrent (limit value 1) are ex-
ceeded for the period of delay time.
GB
Gen.overcurr. 2
D
Gen.-Überstrom 2
Alarm message: Generator overcurrent, limit value 2 Alarm class:
The limit values for monitoring the generator overcurrent (limit value 2) are ex-
ceeded for the period of delay time.
GB
Batt.undervolt.
D
Batt.-Unterspg.
Alarm message: Battery undervoltage
Alarm class: 1
The limit values for monitoring the battery undervoltage are under-run for the period
of delay time.
GB
Pickup/Gen.Freq
D
Pickup/Gen.Freq
Alarm message: Plausibility Pickup/Frequency
Alarm class: 3
This alarm message is shown in the display if the Pickup speed deviates excessive-
ly (
≈
10 Hz) from the generator frequency.
GB
Interf.err. X1X5
D
Fehl.Schnit.X1X5
Alarm message: Interface fault X1-X5
Alarm class: 1
Interface X1..X5 malfunction. External control signals cannot be received.
GB
Interf.err. Y1Y5
D
Fehl.Schnit.Y1Y5
Alarm message: Interface fault Y1-Y5
Alarm class: 1
Interface Y1..Y5 malfunction. External control signals cannot be received.
GB
GCB syn.failure
D
Synch.Zeit GLS
Alarm message: Synchronization time GCB exceeded Alarm class:
If the synchronization time or the connect time for the GCB has been exceeded,
this message is shown in the display. At the same time, an alarm class F1 alarm is
output.
GB
MCB syn.failure
D
Synch.Zeit NLS
Alarm message: Synchronization time MCB exceeded Alarm class:
If the synchronization time or the connect time for the MCB has been exceeded,
this message is shown in the display. At the same time, an alarm class F1 alarm is
output.
GB
GCB syn.failure
D
Zuschaltzeit GLS
Alarm message: Connect time GCB exceeded
Alarm class: 1
If the connect time of the GCB has been exceeded, this message is shown in the
display. At the same time an alarm of alarm class F1 is output.