TD_PCM1x_Packages_Function/Operation_08.04_GB 21
3.2.3
Status Of Power Circuit Breakers And Relays During Synchronization
Rel.: MCB
f U GCB
only visible, while
configuration mode
is active
Status of power circuit breakers and relays of the controllers
The display shows the actual relay states of the controller outputs and the signals to the
power circuit breakers during synchronization.
f
.................. +
Frequency controller RAISE
Terminal 8/9
................... -
Frequency controller LOWER
Terminal 8/10
U
................. +
Voltage controller RAISE
Terminal 11/12
................... -
Voltage controller LOWER
Terminal 11/13
MCB
............ On
Connect pulse of the MCB
Terminal 16/17
................... Off
Disconnect pulse of the MCB
Terminal 39/40
GCB
............ On
Connect pulse of the GCB
Terminal 14/15
................... Off
Disconnect pulse of the GCB
Terminal 41/42