Before performing the adjustments, first check the connections for compliance. Switch on
the installation by pushing the “power” button (I).
The red and yellow light-emitting diodes flash. If not, check the electric connections.
Fitting a retarctile sheath and anti-humidity lugs
Use the blue lugs for the end-of-stroke
sensor and the yellow lugs for the motor
wires whose sections are less than 6
mm²
Engage the wires in the lug
Use crimping pliers to immobilize the
wires
heat it slightly to make it water-
tight
Use the retractile sheath for the motor
wires whose sections are more than 6
mm²
Place the sheath on the wires. Then knot both
wires together before positioning the sheath on
the wires. Then heat it slightly.
INFORMATION ON SWITCH BOX AN 1030
For information about the installation (electric connections and adjustments), refer to the instructions
1-Compatibility :
For PL 3000 motor, use an ATO 25 A fuse (automobile type).
For PL 3200 motor, use an ATO 15 A fuse (original fuse); for double motor, use an ATO 25 A fuse.
Incompatible with DL 1300 and DL3000 motors (mechanical end-of-strokes), use a switch box AN 1010.
2-Power supply 240 VAC :
Terminal board to the far right of the card (any other connections would lead to destruction)
Power indication: green (permanent) LED situated at the right of the card.
3-Forced mode : (red switch)
Sensor input inhibited
Overload detector inefficient
WARNING: using the forced mode means programming the end-of-stroke again.
4-LED signal “motor” sensor (small green LED above of the sensor terminal board)
Motor stopped : led on or off
Motor stopped, sensor is functioning correctly : led flashes regularly
Motor running, sensor with malfunction : led does not flash or off
Note : in case of malfunction, (normal or programming mode), the motor stops and the red “overload” LED flashes, check the connections and the sensor
connections.
5-Auxiliary relay (to activate an electrolysis system or other)
Description: 3 A dry contact 30 VDC, with common contact (c) and de-energized (r) /energized (t) contacts.
Normal mode with shutter completely open : relay energized (t)
Normal mode with shutter in intermediate position or closed : relay de-energized ®
Forced mode, the relay is in the last direction of the key control :
opening direction: relay de-energized
closing direction: relay energized
6-Box fixing
Use the 4 holes at the 4 corners of the box (conical holes for screw centering).
If this type of fixing is not respected, this may lead to cancelling the guarantee
oder