SAFETY CONSIDERATIONS
IMPORTANT SAFETY CONSIDERATIONS
Solid fuel exhaust contains creosote and other substances that accumulate in ducting, creating a risk of fire� The rate
of accumulation will vary with respect to flue gas temperature, wood type and moisture content� Frequent, regularly
scheduled, thorough flue cleaning is the best way to minimize the risk of flue fires� As with all commercial cooking
equipment exhaust systems, a regular inspection and cleaning schedule is needed to prevent the possibility of a hood
or duct fire� The frequency of inspection and cleaning will depend on hours of use and type and quality of wood used
as fuel (see below)� Only use hardwood species dried to a moisture content of 20% or less� See the FUELWOOD FACTS
section at the end of this manual�
CREOSOTE - AND THE NEED FOR ITS REMOVAL
When wood is burned slowly, it produces tar and other organic vapors, which combine with expelled moisture to form
creosote� The creosote vapors condense in the relatively cool oven flue of a slow-burning fire� As a result, creosote
residue accumulates in the duct� When ignited, this creosote makes an extremely hot fire� The duct serving this oven
should be inspected at least twice a month during the first two months of operation, to establish rate of creosote
buildup and necessary cleaning schedule� If creosote or soot has accumulated, it should be removed to reduce the
risk of a flue fire� The interior floor and dome of the oven do not require creosote or soot removal� The oven flue and
exhaust system will require inspection and cleaning�
The oven flue and exhaust system will require inspection and cleaning� The exhaust system should be inspected and
cleaned per the manufacturer’s and or local code official’s recommendations� Typically, ventilation systems serving
solid fuel cooking should be inspected and cleaned at least monthly� Wood Stone recommends cleaning and inspection
at least monthly on any ventilation system serving solid fuel equipment�