VENTING DO’S AND DON’TS
HOOD INSTALLATION WITH DECORATIVE FACADE WALL/OVEN ENCLOSURE
For installations where a hood is being used with a decorative facade wall or oven enclosure, it will be necessary to
both seal the gap between the facade wall and the top of the oven, and the gaps at the sides of the hood between the
facade wall and the front of the oven� This will prevent air from being pulled up the sides of the oven from below by the
hood� It will also prevent debris, etc� from falling into the facade wall�
Note that the hood extends out beyond the face of the
oven� DO NOT extend the oven facade wall into the oven
hood� The wall beneath the hood must stop at the top
of the oven� To allow for proper function of the hood,
filter removal and hood maintenance, you must provide
a minimum of 8 inches of clearance between the front
face of the facade wall and the front of the hood�
Additional flashing detail
Wall stud
Shield
flashing
to be
flush
with
top of
oven
Flashing piece
by installer
Acceptable venting
Acceptable venting