120 VAC Oven Circuit
120 VAC
to Oven
S1 is a Double Pole, Single Throw (DPST)
switch provided by others.
120 VAC
to Fan
Wired by others
S1
120 VAC Fan Circuit
INTERLOCK OF OvEN CONTROL TO AN EXHAUST FAN
this connection is intended to interrupt power to the oven until the fan is turned on�
S1 is a double pole, single throw switch (provided by others) that interrupts in-coming power to both the oven and the
fan� the intent is to prevent the operation of the oven’s gas burner in the event the fan is shut off�
any interruption of the power to the oven will cause the oven (including all burners and pilots) to shut off, and it will be
necessary to restart the oven by pressing the start switch once power is restored�
For additional interlock options, see the Wood Stone interlock Options supplement in the manuals section on the website,
woodstone-corp.com
, or contact Wood Stone for additional information�