MULTISETWORKS OPERATION (OPTIONAL EQUIPMENT)
Errors
MULTISETWORKS OPERATION (OPTIONAL EQUIPMENT)Multisetworkdoc012819
3-19
3
See Figure 3-22.
Make sure if COF error is displayed on the drive controller after opening electric box.
CAN_R LED should be steady on, I/O and CAN_E LED should blinks red:
See Figure 3-23.
If so, check connection between drive and cantap (patchcord with RJ45 terminals). When two or
more saw heads are missing, check connection between cantaps and PLC controller. Next turn off and turn
on the power to restart the connection. Connection condition can be also check on the Diagnostic screen by
FIG. 3-22
FIG. 3-23