System Operations
System 4
Time Clock (1 Valve)
During normal operation the
Time of Day
display may be viewed at all times. The control operates normally
until the number of days since the last regeneration reaches the
Regeneration Day Override
setting. Once
this occurs, a
Regeneration Cycle
initiates at the preset
Regeneration Time
.
Meter Delayed (1 Valve)
During normal operation the
Time of Day
display alternates with the
Volume Remaining
display
(gallons or m
3
).
— As treated water is used, the
Volume Remaining
display counts down from the calculated system
capacity.
— The system monitors the volume of water used. When the system calculates that there is not a sufficient
capacity for the next day’s operation, a regeneration cycle is initiated at the preset regeneration time.
— Water flow through the valve is indicated by the Flow Dot that flashes in a direct relationship to flow rate.
Meter Immediate (1 Valve)
During normal operation the
Time of Day
display alternates with the
Volume Remaining
display
(gallons or m
3
).
— As treated water is used, the
Volume Remaining
display counts down from the calculated system
capacity to zero or (----). When this occurs a
Regeneration Cycle
is started.
— Water flow through the valve is indicated by the Flow Dot that flashes in a direct relationship to flow rate.
System 5
Interlock (2 – 4 Valves)
During normal operation the
Time of Day
display alternates with the
Volume Remaining
display
(gallons or m
3
).
— As treated water is used, the
Volume Remaining
display counts down from the calculated system
capacity to zero or (----). When this occurs a
Regeneration Cycle
queues.
— If no other valve is in
Regeneration
the valve sends a lock command and starts a
Regeneration Cycle
.
— If another valve is in
Regeneration
(i.e. the system is already locked) the valve remains
In Service
with
Regeneration
queued until other valves complete
Regeneration
. Then the system locks and
Regeneration
begins.
— Water flow through the valve is indicated by the Flow Dot that flashes in a direct relationship to flow rate.
System 6
Series (2 – 4 Valves)
During normal operation the
Time of Day
display alternates with the
Volume Remaining
display
(gallons or m
3
). The
Volume Remaining
is the total volume for all units in the system.
— As treated water is used, the
Volume Remaining
display counts down from the calculated system
capacity to zero or (----). When this occurs a
Regeneration Cycle
queues.
— If no other valve is in regeneration the lead valve sends a lock command and starts a
Regeneration
Cycle
.
— When the LEAd valve completes regeneration cycle the remaining valve(s) in the system regenerate
sequentially until all valves regenerate.
— Water flow through the valve is indicated by the Flow Dot that flashes in a direct relationship to flow rate.
— LAg valve volume remaining is updated every 5 seconds from the LEAd valve.
— A manually forced regeneration (EC key) can only be done on the LEAd valve and only if the system is not
in
Regeneration
.