3200NT Timer
4
Timer Operation
Set Time of Day
When the timer is
In Service
, push either the
Set Up
or
Set Down
button once to adjust the
Time of Day
by
one digit. Push and hold to adjust by several digits.
Manually Initiating a Regeneration
1.
When timer is
In Service
, press the
Extra Cycle
button for 5 seconds to force a manual regeneration.
2.
The timer reaches
Regeneration Cycle
Step #1.
3.
Press the
Extra Cycle
button once to advance valve to Regeneration Cycle Step #2 (if active).
4.
Press the
Extra Cycle
button once to advance valve to Regeneration Cycle Step #3 (if active).
5.
Press the
Extra Cycle
button once to advance valve to Regeneration Cycle Step #4 (if active).
6.
Press the
Extra Cycle
button once to advance valve to Regeneration Cycle Step #5 (if active).
7.
Press the
Extra Cycle
button once more to advance the valve back to
In Service
Timer Operation During Regeneration
In the
Regeneration Cycle
step display, the timer shows the current regeneration step number the valve is
advancing to, or has reached, and the time remaining in that step. The step number that displays flashes until
the valve completes driving to this regeneration step position. Once all regeneration steps are complete the
timer returns to
In Service
and resumes normal operation.
Example:
Start a Regeneration Tonight
With metered delayed timers, press the
Extra Cycle
button momentarily. The
In Service
indicator dot flashes
and starts a
Regeneration
tonight at the programmed
Regeneration Time
.
Day Regeneration Timer
During normal operation the
Time of Day
display is visible at all times. The timer operates normally until the
number of days since the last regeneration reaches the
Regeneration Day Override
setting. Once this occurs,
a regeneration cycle is initiated at the preset
Regeneration Time
.
Flow Meter Equipped Timer
During normal operation the
Time of Day
display alternates with the
Volume Remaining
display
(gallons or m
3
).
— As treated water is used, the
Volume Remaining
display counts down from the calculated system
capacity to zero or (----). When this occurs a
Regeneration Cycle
begins or delays to the set
Regeneration Time.
— Water flow through the valve is indicated by the Flow Dot that flashes in a direct relationship to flow rate.
Less than 10 Minutes Remaining in Regen Step #1
Press the
Extra Cycle
button during a
Regeneration
Cycle
to immediately advance the valve to the next cycle
step position and resume normal step timing.
Содержание 3200NT
Страница 24: ...P N 41093 Rev B 02 04 ...