background image

23

14.

 

FULL OPERATING CHECKS

14.1

Recheck Control Settings

Now that all the ceramic fuel effects are in position, the control operation must be fully
rechecked.

14.1.1

Make sure that the isolating valve at the inlet elbow is open and that the electrical

power supply is on (the indicator light should glow).

14.1.2

Press and hold in the “on” switch. Within two seconds, the Fan motor should

start and the indicator light should go out.

14.1.3

Release the “on” switch. The fan should continue to run.

14.1.4

Depress the control knob and turn anticlockwise partially towards the

“PILOT/IGN” position until some resistance is felt.  Keep depressed at this position to
purge air from the system then, while keeping it depressed, turn fully to the
“PILOT/IGN” position.  A spark should be generated at the pilot while turning. The
spark should ignite the pilot. Check that the pilot flame is visible.

14.1.5

When pilot ignition has been achieved, keep the control knob depressed for

approximately ten seconds to allow the thermocouple probe to warm up and then release
it. If the pilot does not remain alight, ensure that the pilot orifice is clear.

14.1.6

When the pilot is alight and stable, partially depress the knob and turn to “LOW”.

The pilot should then light the main burner at its low setting. There may be a delay of up
to four seconds between the pilot lighting and ignition of the gas at the main burner.  This
is normal and is due to the time required to fill the main burner compartment with
sufficient gas for ignition.

14.1.7

When the burner is operating properly, partially depress the knob and gradually

turn it anti-clockwise. The burner flames should gradually increase until the knob reaches
the “HIGH” position.

14.1.8

Partially depress the control knob and turn back to “PILOT/IGN”. The main

burner flames should be extinguished but the pilot should remain alight.

14.1.9

Partially depress the control knob and turn to “OFF”. The pilot should be

extinguished.

14.1.10

Press the “off” switch to turn off the fan (the indicator light should glow).

14.2

Check For Spillage

A spillage check must be made before leaving the installed appliance with the customer. Make
this check with the appliance fully installed with the ceramic fuel effects and front surround
in position.
14.2.1

Close all doors and windows in the room containing the appliance.

14.2.2

Turn on the fan

Light the appliance. Turn the control to “HIGH”.

14.2.3

Leave the appliance on for five minutes.

14.2.4

Place the smoke match tube into the convection box at the right hand side and

immediately below the black top cross member. Angle it at approximately 45° to the
horizontal(fig. 43).
Insert the tube so that the neck of its flared end touches the inside surface of the edge of
the cross member (figure 43).
Keeping the neck of flared end in contact with the edge of the cross member, slide the
tube to the left until you feel it enter the notch in the edge of the cross member. Make
sure that the tube is pointed upwards at 45º to the horizontal.
The installation is satisfactory if the smoke is drawn into the appliance. If the smoke is not
drawn into the appliance the powered fan is not operating correctly. 

Do not allow the

appliance to be used until the fault is corrected.
14.2.5

If the above test is satisfactory, open all internal connecting doors, hatches, etc. in

the room. Switch on any extractor fan or other air circulating system installed in the same
room as the appliance or in a connecting room. Keep all doors and windows that open to
the outside of the building closed. Recheck for spillage as above.
If the smoke is drawn into the appliance, continue with the installation. If the test is not
satisfactory, 

disconnect the appliance and advise the customer of the cause of failure.

14.2.6

If any other non-sealed gas appliances are installed in the room or connecting

rooms, check that to ensure that there is no spillage from these appliances when Model

  

 

Figure 43 Smoke match tube

  

        position

Содержание Lincoln BR517S

Страница 1: ...I N S T A L L E R G U I D E For MODEL BR517S G C 3 2 0 3 2 1 2 S i d e F a n F l u e d I n s e t G a s F i r e with LINCOLN Front Please keep in a safe place for future reference 600B416 02...

Страница 2: ...us on 0121 386 6203 In the republic of Ireland call 353 183 75114 P l e a s e l e a v e t h i s I n s t a l l e r G u i d e w i t h t h e u s e r As supplied this appliance is for use with natural gas...

Страница 3: ...NSTALLATION 22 14 FULL OPERATING CHECKS 23 15 FINAL REVIEW 25 16 SERVICING PARTS REPLACEMENT 26 16 1 To Replace Burner Plaques See Figure 44 26 16 2 To Remove The Front Surround 27 16 3 To Remove The...

Страница 4: ...thing is not required when handling these articles but we recommend you follow the normal hygiene rules of not smoking eating or drinking in the work area and always wash your hands before eating or d...

Страница 5: ...Rules for Electrical Installation 2 2 Electrical isolation of the unit should be by means of a switched fuse spur that should be readily accessible to the user easily identifiable and preferably sited...

Страница 6: ...6 Figure 1 General Installation Dimensions...

Страница 7: ...rround the burner bracket and the bottom front cover casting to be aligned horizontally Any excessive unevenness uneven tiles Cotswold stone etc should be rectified The appliance must not stand on com...

Страница 8: ...ld be located so that the wind can blow freely across it at all times and where any blockage due to leaves snow etc is unlikely The minimum allowable distances from the terminal are shown in the follo...

Страница 9: ...ls 1 Pipe bending template 1 Surround cutting metal template 1 Smoke match tube 1 Terminal weather shield 1 Junction box with cable clip earth lead sleeve fixings 1 Pack of fixings 1 Literature pack 1...

Страница 10: ...ob and while keeping it depressed turn anticlockwise through approximately 60 to the PILOT IGN position A spark should track from the electrode pin to the thermocouple tip If there is no spark or inco...

Страница 11: ...see figure 8 Carefully pull the unit slightly forward 3 Detach the control unit cover by removing one screw See figure 9 4 Remove the cable by releasing the cable clamp and detaching the leads from th...

Страница 12: ...om the rear left of the convection box Replace the screw thus removed into the convection box Clamp the cable at one of the screws at the right side of the box see figure 11 6 7 Fit the flue duct conn...

Страница 13: ...the outer wall make a rectangular opening as shown in figure 15 The depth of the recess is 145mm leaving the 50mm minimum projection required outside the wall Note that the fan box is not designed to...

Страница 14: ...nnection spigot in the hole in the wall and if applicable the fan box in the recess Push the box in so that the fixing brackets are against the wall and mark the screw fixing positions on the wall 7 3...

Страница 15: ...tween the top horizontal flanges or bottom angled flanges of the backing plates 8 3 Measure the length of the duct run between the intersection of the horizontal and sloping sections of the Z coupling...

Страница 16: ...fan cable into the C sections at the bottom of the support brackets see figure 24 8 11 Further support for the fan cable especially at corners can be provided using the spring cable clips supplied in...

Страница 17: ...he corners 8 15 For vertical duct installations Normally a false chimney breast will be constructed to hide the ducting The duct front covers will not therefore be required for these installations but...

Страница 18: ...erminal The fan should be heard to increase to boost speed within approximately two seconds iii Remove the hand The fan should revert to normal speed after approximately three seconds 9 6 The unit inc...

Страница 19: ...n position aligning the holes in the shield with those at the sides of the end plate Secure with the two screws previously removed see figure 32 10 3 Fit the terminal guard see figure 33 Secure the gu...

Страница 20: ...on box Carefully lift the cast front into position square with the convection box taking care not to damage the slide control mechanism Holding the cast front a little above the top surface of the con...

Страница 21: ...ght ensure that the air has been purged that the pilot orifice is clear and that the thermocouple connections are sound Replace the pilot unit if necessary see servicing section of this manual 12 3 7...

Страница 22: ...ner compartment and its rear face should touch the rear ceramic wall See figure 39 13 4 Install the 9 loose coals as follows The smooth surfaces of the coals should be at the bottom and back 13 4 1 Se...

Страница 23: ...depress the control knob and turn to OFF The pilot should be extinguished 14 1 10 Press the off switch to turn off the fan the indicator light should glow 14 2 Check For Spillage A spillage check must...

Страница 24: ...for one minute 14 3 2 Turn back to OFF to extinguish the pilot Note the time when the pilot goes out Listen for a snap sound at the gas tap Note the time when the sound is heard This sound is caused...

Страница 25: ...s that if the monitoring system repeatedly shuts off the fire the appliance should be switched off and a specialist should be consulted 15 6 Advise the customer that they should read their Owner s gui...

Страница 26: ...lls and coals are replaced correctly as described in the installation instructions Always test for gas soundness and spillage after servicing the appliance and check operation of all controls Do not u...

Страница 27: ...disconnect the appliance from the elbow 16 3 4 Detach the burner unit from the convection box by removing 2 screws see figure 46 Carefully lift the burner unit forward making sure that the unit does n...

Страница 28: ...ove the gas tap solenoid unit as sections 16 5 1 to 16 5 12 16 6 2 Make sure that the tap is in the off position 16 6 3 Remove the circlip holding the piezo unit to the tap Remove the piezo unit 16 6...

Страница 29: ...witch see figure 53 16 10 5 Disconnect the three leads Yellow orange white from the air pressure switch 16 10 6 Disconnect the two leads Brown blue from the mains cable connection block 16 10 7 Replac...

Страница 30: ...weather shield and flue box end plate by removing two screws see figure 55 16 12 3 Disconnect the wiring loom connector inside the top right of the flue box see figure 56 15 12 4 Slide the fan out of...

Страница 31: ...709 D Gas tap spark generator 1 545969 E Spark generator 1 521069 F Control knob 1 545979 G Pilot unit For Natural Gas Appliances 1 540979 Pilot unit For Propane Appliances 544929 H Solenoid valve 1 5...

Страница 32: ...tered Installer Please fill in the following information for your own future reference The information should always be quoted in any correspondence with your original supplier or Wonderfire service d...

Отзывы: