9 Commissioning
FWL-PushPull-30 (TwinUnit)
46 | WOLF GmbH
7100904 | 202202
9.3 FWL-PushPull RLS-K service menu
Bol
d
Factory settings
LED flashes quickly
LED flashes slowly
LEDs
Parameters
Set value /
ventilation
level
Setting /
description
Device type on
FWL-PushPull
(Fan1/Fan2)
1
2
FWL-PushPull-45
Here, the type family, which is
connected to the Fan1/Fan2 inter-
face, is selected.
Notice: Only single-type FWL-
PushPull-45 or FWL-PushPull-30
unit combinations are permitted at
the fan interface!
Number of device pairs/
devices on
FWL-PushPull
(Fan1/Fan2)
1
2
3
4
5
1 FWL-PushPull-45 unit pair or
1 FWL-PushPull-30
2 FWL-PushPull-45 unit pairs or
2 FWL-PushPull-30
3 FWL-PushPull-45 unit pairs or
3 FWL-PushPull-30
Odd number 3 FWL-PushPull-45
units
Odd number 5 FWL-PushPull-45
units
The number of units connected to
the fan interface (Fan1/Fan2) is
selected here. Notice: Release/
number of FWL-PushPull-30 units
is taken into account in another
sub-menu (FWL-PushPull-30
parameters)
Ventilation levels
1
2
Ventilation level “0” possible
Ventilation level “0” blocked
If ventilation level “0” is set to
blocked, the ventilation units can-
not be switched off at this control.
The units then run with at least
ventilation level 1.