9 Commissioning
FWL-PushPull-30 (TwinUnit)
42 | WOLF GmbH
7100904 | 202202
9 Commissioning
Basic settings on the room air control are under-
taken in service mode. If connected to
FWL-
PushPull RLS-K
, the commissioning software
may also be used.
Switch on ventilation system as follows:
1. Ensure that all ventilation units and system
components are connected to the room air
controls.
2. Remove warning sign from fuse box and
switch on mains fuse. The ventilation units
start up in ventilation level 2.
3. Run function test.
4. Set the desired parameter values in
Service
mode
or using the commissioning software.
Basic settings can be made directly on the
FWL-PushPull RLS or FWL-PushPull RLS-K
room air control unit. To do this, select Ser-
vice mode and set the desired parameter
value. Additional information can be found in
the online commissioning instructions (down-
load at www.WOLF.eu). Here you can also
download the commissioning software for the
FWL-PushPull RLS-K control. This provides
you with a wide range of setting parameters
for individual system adjustments.
9.1 Service mode – operation
Starting service mode
+
Press both
buttons for
5 seconds.
Operating
mode LED
flashes. You
are in the 1st
submenu
(number of unit
pairs, ventila-
tion level, etc.)
→ following
chapters.
+
+
Cycle: selecting parameter
You can
switch
between the
sub-menus
by pressing
the button
once.
Flashing oper-
ating mode
LEDs show in
which sub-
menu item you
are*/** → fol-
lowing
chapters.
/
* Illuminated ventilation level LEDs indicate the
parameter currently set.
** For
FWL-PushPull-45 RC
, the red flashing
LED indicates the currently set parameter.
Changing parameter value
Once you
have reached
a certain sub-
menu, the
parameters
can be set
with these
buttons.
Once the para-
meter has
been changed,
the ventilation
level LEDs
flash.
/
Saving parameter value
To save,
press the but-
ton for 2
seconds.
The parameter
value is now
accepted.*/**
+
* The ventilation level LEDs light up permanently
again.
** On RC units, all 3 LEDs light up and then go
out one after another. Parameter value is adop-
ted, service menu is exited.
Exiting service mode
+
Press both
buttons for
5 seconds.
The unit
switches back
to the current
ventilation
mode/ventila-
tion level.
If no button is
pressed for
120 seconds
in service
mode, service
mode is auto-
matically ex-
ited.
+
+