8 Installation
FWL-PushPull-30 (TwinUnit)
7100904 | 202202
WOLF GmbH | 41
8.8 Installing radio switch (EnOcean)
When radio mode is activated, EnOcean radio
components, such as master or slave units or
sensors, can be taught-in directly on ventilation
units. For range of radio components →
Technical
data [
}
33]
.
Purely radio-
controlled
system
Combination system
FWL-PushPull
RLS-RC
FWL-PushPull
RLS-K
FWL-PushPull
RLS-LTRC
+
+
+
FWL-Push-
Pull-45 RC
FWL-Push-
Pull-45 RC
FWL-Push-
Pull-30 RC
(TwinUnit)
max. 6
FWL-Push-
Pull-45
FWL-Push-
Pull-45 RC
FWL-Push-
Pull-30 RC
(TwinUnit)
...
or
max. 3
/
FWL-Push-
Pull-30 (Twin-
Unit)
Installation location: Do not mount re-
ceiver, with internal antenna, on wall side of
transmitter.
Purely radio-controlled FWL-PushPull-45 sys-
tem
1. Simply glue
FWL-PushPull RLS-RC
to install-
ation location on the wall. Alternatively, the ra-
dio switch can also be screwed onto the wall
(mounting material provided by customer).
2. Use the "Learn button" to activate teaching-in
mode on the ventilation unit. For more detailed
information on teaching-in → Operating in-
structions.
3. For basic unit settings, such as “Block Off
function” → Installation instructions.
FWL-PushPull-45 combination system with
FWL-PushPull RLS-LTRC
Extension module FWL-PushPull RLS-LTRC
can only be combined with FWL-PushPull-45
RC unit pairs. Wired operation is needed for
other unit types.
1. Install the
FWL-PushPull RLS-LTRC
EnOcean extension module. For more inform-
ation → Accessories instructions. If necessary,
plan a separate distribution box for the wiring.
2. Connect EnOcean extension module to
FWL-
PushPull RLS-K
control (RS485)→
Connec-
tion and wiring diagrams [
}
54]
3. Start up ventilation system, activate in
EnOcean service mode → .
4. Slide the slide-in module (
FWL-PushPull-45
/
FWL-PushPull-45 RC
), inside the sleeve, as
far as possible towards the exterior wall.. NO-
TICE: Connecting cable must not be installed
tautly.
8.9 Installation of humidity sensor
FLW-PushPull RH Sensor int. in
FLW-PushPull RLS / RLS-K
1. Install room air control as described before.
NOTICE: Unit damage/no function if the hu-
midity sensor is installed incorrectly. Do not
bend pins. Insert sensor up to stop in bush.
2. Insert
FWL-PushPull RH Sensor int.
humidity
sensor at I2C interface → Arrow.
3. Fit frame. Make sure it locks into position.
The frame has NO protection against twist-
ing. Ensure that sensor opening (hole in frame)
is above the sensor.
4. Start up ventilation system and register humid-
ity sensor in service mode→..
For installation and wiring of an external sensor→
FWL-PushPull-45
/
FWL-PushPull-30 (Twin-
Unit)
installation and commissioning instructions.