8  GENERAL OPTION

• 

Connect the handset to RJ45 connector;

• 

If necessary, using keys 

ã

 and 

ä

 choose the required language and confirm with the “OK” key

• 

Using keys 

ã

 and 

ä

 run through the MAIN MENU and choose GENERAL OPTIONS

• 

Press OK to confirm the choice

• 

The GENERAL OPTION menu allows the Door Controller to operate by means of the following parameter options:

 

REVERSING SYSTEM

 

MAIN LIFT CONTROLLER TEST

 

NO MLC SIGNAL

 

MLC INPUT ALARM

 

LIMITED DOOR REVERSAL

 

CAR DOOR LOCKING DEVICE

 

GLAZED PANELED DOORS

 

AUX OUTPUT RELAY

 

PROTECTIVE DEVICE LOGIC

 

EMULATION TYPE

These parameter meanings and settings are detailed in the following paragraphs.

8.1  REVERSING SYSTEM SETTING BY MEANS OF THE HANDSET

• 

See 

“6.1 Reversing system force setting” a pag. 19

 for the meaning of this parameter

• 

Using keys 

ã

 and 

ä

 run through the GENERAL OPTIONS and choose the option REVERSING SYSTEM

• 

Press the “OK” key to confirm the choice

• 

The following options are viewed on the display:

 

INTERNAL

 

EXTERNAL

• 

Using keys 

ã

 and 

ä

 choose the required option and press the “OK” key to confirm it

• 

The display shows the confirmed option and restores the menu GENERAL OPTIONS

• 

The following options are available:

 

“BACK”: Press key F1 to restore the menu GENERAL OPTIONS

 

“MENU”: Press key F3 to restore the MAIN MENU

8.2  ACTIVATION OF THE MAIN LIFT CONTROLLER TEST BY MEANS OF THE HANDSET

• 

See 

“6.4 Main Lift Controller Test” a pag. 19

 for the meaning of this parameter

• 

Using keys 

ã

 and 

ä

 run through the GENERAL OPTIONS and choose the option MAIN LIFT CONTROLLER TEST

• 

Press the “OK” key to confirm the choice

• 

The following options are viewed on the display:

 

WHEN MOVING

• 

The display shows the confirmed option and restores the menu GENERAL OPTIONS

• 

The following options are available:

 

“BACK”: Press key F1 to restore the menu GENERAL OPTIONS

 

“MENU”: Press key F3 to restore the MAIN MENU

8.3  ACTIVATION OF THE MAIN LIFT FAILURE BY MEANS OF THE HANDSET

• 

See 

“6.4.1 No MLC Signal” a pag. 19

 for the meaning of this parameter

• 

Using keys 

ã

 and 

ä

 run through the GENERAL OPTIONS and choose the option NO MLC SIGNAL

• 

Press the “OK” key to confirm the choice

• 

The following options are viewed on the display:

 

IMMEDIATELY STOP

• 

The display shows the confirmed option and restores the menu GENERAL OPTIONS

• 

The following options are available:

 

“BACK”: Press key F1 to restore the menu GENERAL OPTIONS

 

“MENU”: Press key F3 to restore the MAIN MENU

8.4  MAIN LIFT CONTROLLER ALARM - (MLC INPUT ALARM)

• 

See 

“6.4.2 Main Lift Controller Input Alarm” a pag. 19

 for the meaning of this parameter

• 

Using keys 

ã

 and 

ä

, run through the GENERAL OPTIONS and choose the option MLC INPUT ALARM

• 

Press key “OK” to confirm the choice

• 

The following options are viewed on the display:

 

OFF

 

ON

• 

Using keys 

ã

 and 

ä

, choose the required option and press the “OK” key to confirm it

• 

The display shows the confirmed option and restores the menu GENERAL OPTIONS 

• 

The following options are available:

 

“BACK”: Press key F1 to restore the menu GENERAL OPTIONS

 

“MENU”: Press key F3 to restore the MAIN MENU

8.5  LIMITED DOOR REVERSAL ACTIVATION BY MEANS OF THE HANDSET

• 

See 

“6.3 Limited Door Reversal” a pag. 19

 for the meaning of this parameter

Содержание sematic DC-PWM Compatible

Страница 1: ...com Copyright WITTUR 2020 SDS Drive DC PWM Compatible No part of this publication may be reproduced or translated even in part without prior written permission from WITTUR Subject to change without no...

Страница 2: ......

Страница 3: ...ches 16 5 Instruction without handset 17 5 1 Automatic Mode AUTO 17 5 2 Manual Mode MAN 17 5 3 Programming Mode PROG 17 6 Functions available 19 6 1 Reversing system force setting 19 6 2 Reversing Sys...

Страница 4: ...ntroller Alarm MLC Input Alarm 27 8 5 Limited door reversal Activation by means of the handset 27 8 6 Activation of the Car Door Locking Device setting by means of the Handset 28 8 7 Activation of the...

Страница 5: ...System shall not be disclosed to anyone without Sematic s written consent apart from authorized representatives employed by the user which commits itself to the confidentiality clause The Company tha...

Страница 6: ...PONENT SYSTEMS Automatic lift doors Frame and frameless glass doors Enhanced car door operator solutions Complete cabins Car Frames Custom integrated packages Special lift doors cabins and car frames...

Страница 7: ...since the following conditions have not been ensured 1 Quality control of raw material supply 2 Process control 3 Product control 4 Conformity tests according to Sematic specifications Furthermore Sem...

Страница 8: ...fied by means of the door controller push buttons or by means of the Sematic handset an optional 8 digit keypad and display accessory which can be connected to the card by an RJ45 plug The handset 6 i...

Страница 9: ...e Instruction Manual 2 1 SPEED PROFILE Opening cycle O1 Opening acceleration O2 Opening hight speed O3 Opening deceleration Closing cycle C1 Closing acceleration C2 Closing hight speed C3 Closing dece...

Страница 10: ...x20 4 A battery fuse 5x20 8 A PERFORMANCE SPEED separately adjustable for opening and closing REVERSAL SENSITIVITY Variable only operational on door closing cycle 3 2 SEMATIC DRIVE SYSTEM DOOR CONTROL...

Страница 11: ...uly 2020 Drive Instruction Manual 4 SIGNALS TO FROM THE DOOR CONTROLLER 4 1 SEMATIC DRIVE SYSTEM DC PWM COMPATIBLE CONNECTIONS DOOR POSITION LC SWITCH STATE RC SWITCH STATE RA SWITCH STATE LA SWITCH S...

Страница 12: ...04923 EN 811 000 000 SDS DC PWM Compatible Edition 22 July 2020 Drive Instruction Manual 4 2 SEMATIC DRIVE SYSTEM SET UP AND INCOMING OUTGOING SIGNALS FROM THE DOOR CONTROLLER 1 Magnetic switches 2 Sa...

Страница 13: ...ilures Re opening control Kn Connector pins 15 23 These connections require dry voltage free contacts both logics available See 4 1 4 2 for the connection to the door controller Closing limit switch c...

Страница 14: ...istance has been achieved or as a Gong or Buzzer while the door is opening or as a Thermic alarm signal Contact rating 3A 250Vac 30Vdc Connector pins 35 36 contact normally closed Motor Connector pins...

Страница 15: ...s through dummy connector pin for connections between the detector system components 1 Example of photocells barriers with transmitter and receiver connected between themselves through the dummy free...

Страница 16: ...are the operations of the magnetic switches Closed door the door close limit pre adjusted by the manufacturer must operate when the carriage has already stopped but the retractable skate is not close...

Страница 17: ...3 sec the Door Controller switches to the automatic mode AUTO If no keys are pressed for at least 10 minutes the Door Controller will switch to the automatic mode AUTO Both in automatic and manual mo...

Страница 18: ...t Relay 00 01 02 03 00 Off 01 Gong While opening 02 According to of space 03 Termic Alarm signal 08 00 Space Percentage Percentage of the available space o operate the AUX relay 00 99 00 99 00 closing...

Страница 19: ...or this setting the main lift controller must be equipped with 2 relays 1 for the opening command and 1 for the closing command The Door Controller checks for continuous presence of the Ka and Kc sign...

Страница 20: ...d to 23 and 15 terminals 31 and 32 terminal must be shorted 6 10 EMULATION TYPE SDS DC COMPATIBLE controller may replace different kind of old controllers Usig this parameter is possible to select req...

Страница 21: ...r cables Note 4 Auto reset after 5 seconds after 5 occurrences within 5 minutes the system stops 08 Over voltage Over voltage in the power supply Door controller switches to low speed signals the erro...

Страница 22: ...cod B147AABX see picture 3 a 16 mm diameter hole is required in any chosen position within the Car walls Note when the handset is connected to the controller the display shows the warrantly expiration...

Страница 23: ...wittur com Changes can be made without notice PM 2 004923 EN 811 000 000 SDS DC PWM Compatible Edition 22 July 2020 Drive Instruction Manual 7 2 USER HANDSET MENUS AND SUBMENUS only for Digidoor Emul...

Страница 24: ...tings This option allows to easily and quickly modify the speed profiles Choose this option as indicated in the first part of 8 5 Limited door reversal Activation by means of the handset a pag 27 The...

Страница 25: ...ailable BACK press key F1 to restore the MAIN MENU F2 KEY to open and close the door to test the modified profile DRAW press key F3 to update the speed profile drawing 7 5 2 Option Closing Parameters...

Страница 26: ...t Only for digidoor emulation This option allows the user to change the closing rest current delay from the closing limit Lc signal The setted time starts from the Lc switch signal Select the desired...

Страница 27: ...for the meaning of this parameter Using keys and run through the GENERAL OPTIONS and choose the option MAIN LIFT CONTROLLER TEST Press the OK key to confirm the choice The following options are viewe...

Страница 28: ...ay shows the confirmed option and restores the menu GENERAL OPTIONS The following options are available BACK Press key F1 to restore the menu GENERAL OPTIONS MENU Press key F3 to restore the MAIN MENU...

Страница 29: ...l The following options are viewed on the display Emulation F28 Emulation F29 Emulation DIGIDOOR 1Nm Emulation DIGIDOOR 2Nm Emulation LM DC 2010 Emulation LM DC 2011 Using keys and choose the required...

Страница 30: ...on and time of occurrence day hour minute from the door controller start up Using keys and run through the stored alarm list The following options are available BACK Press key F1 to restore the menu M...

Страница 31: ...Press OK to confirm the choice Display shows the last available update and the software version in use at the moment Press OK to confirm the software update Controller operates a reset and the display...

Страница 32: ...a and Rc opening and closing slow down COM 15 7 24 Vac power NOT CONNECTED 8 24 Vac power NOT CONNECTED 9 motor power 43 10 motor power 44 11 Ra opening slow down Input signal 41 12 NOT CONNECTED 13 R...

Страница 33: ...common line for LA and LC switches is different depending on the MLC Es MLC type 1BN H PA Common line 48V MLC type 1BN L PA Common line 0V 7 MAIN LIFT CONTROLLER HMPU 8 Magnetic switches installed on...

Страница 34: ...20 Drive Instruction Manual 12 UPGRADE FROM F28 F29 AND LMDC 2010 2011 DIGIDOOR Short instruction replacement F28 F29 and LMDC 2010 2011 DIGIDOOR 01 F28 03 Digidoor 1 Nm 05 LMDC 2010 02 F29 04 Digidoo...

Страница 35: ...28 29C TERMINALS FUNCTION SEMATIC SDS Rel 3 DC COMPATIBILE 1 IM reversing system N C signal 1 2 IM reversing system N O signal 2 4 IM reversing system COM signal 4 3 Kc closing control 3 5 Ka opening...

Страница 36: ...h COM from the magnetic switch 15 18 IN Lc Closing limit switch input contact from the magnetic switch 39 19 IN La Closing limit switch COM from the magnetic switch 15 Warning If in the old drive F28...

Страница 37: ...G a pag 17 Check the correct functioning F28 29 Rel 2 0 TERMINALS FUNCTION SEMATIC SDS Rel 3 DC COMPATIBILE 1 IM reversing system N C signal 1 2 IM reversing system N O signal 2 4 IM reversing system...

Страница 38: ...X A Select option EMULATION LM DC 2010 or EMULATION LM DC 2011 from the Menu General Option see 8 10 Emulation Type a pag 28 or programm parameter 22 using the keys on the frontal panel 05 o 06 see al...

Страница 39: ...derneath table Connect the 220 Vac input to the SDS controller by means of the feeding cable supplied code no E066AAWX A Select option EMULATION DIGIDOOR 1Nm or EMULATION DIGIDOOR 2Nm from the Menu Ge...

Страница 40: ...door operator toothed belt is tight enough and in good working condition Check and clean the cable connections of the motor and of the motor Encoder 18 SPARE PARTS It is possible to order all the Sem...

Страница 41: ......

Страница 42: ...YOUR GLOBAL PARTNER FOR COMPONENTS MODULES AND SYSTEMS IN THE ELEVATOR INDUSTRY More information about Wittur Group available on line a WITTUR brand a WITTUR brand a WITTUR brand...

Отзывы: