Manual
WITA HE + go.future 40-XX | 50-XX | 60-XX
5.1
Technical data WITA HE + go.future 60-XX
HE + go.future 60-XX
Maximum elevation height
6.0 m
Maximum flow
3500 l/h
Power consumption P1 (W)
3 - 41
Supply voltage
1 x 230V 50Hz
Noise level
< 43 dB(A)
EEI
≤
0.20
Protection type
IP 42
Thermal class
TF 110
Ambient temperature
0°C to 40°C
Medium temperature
+5 to 110°C
Maximum system pressure
10 bar (1MPa)
Permitted pumped media
Heating water according to VDI 2035
Water/glycol mixture 1:1
Supply pressure
Acceptable range of temperature
Attention! The use of unsuitable media can destroy the pump and result in
health damage. It is essential to observe the manufacturer's information
and safety data sheets!
5.2 Delivery
range
• original assembly and operating manuals
• pump
• 2 flat gaskets
• Pump plug
• Insulation
28
Characteristic WITA HE + go.future 60
Medium Minimum
temperature
supply pressure
< 75 °C
0.05 bar 0.005 MPa 0.5 m
75 °C - 90 °C
0.3 bar
0.03 MPa
3.0 m
90 °C - 110 °C
1.1 bar
0.11 MPa
11.0 m
Temperature range at
Permissible
maximum medium
ambient temperature
temperature
25 °C
5 °C to 110 °C
40 °C
5 °C to 95 °C
Advice
0
1
2
3
4
5
6
7
0
1000
2000
3000
4000
mWs
l/h