DiPro 1500 Fault messages
DiPro 1500 User Manual
101
Ch 7
1092000
Sensor failure
SENSOR 4 [sensor name]
SENSOR FAILURE, THIS SENSOR SEEMS TO BE
SHORTED TO GROUND
Problem:
For a green or green constant sensor, the sensor has stayed on from the
end of one ready signal to the beginning of the next ready signal for
the next stroke. No stroke angle is shown with this fault.
Remedy:
Check for a shorted sensor. Make sure the ready signal has been set
correctly. Check to see if a press or equipment malfunction is causing
the sensor to stay on—for instance, a part wedged against a sensor or a
pinched wire.
Green constant fault
SENSOR 1 [sensor name]
THIS GREEN CONSTANT SENSOR WENT OFF IN
ITS READY AT DEGREES
Problem:
A green constant sensor turned off during its ready signal. Green
constant sensors must stay on throughout the entire ready signal. The
angle where the sensor turned off is shown.
Remedy:
Check for the malfunction that the sensor was supposed to detect.
If no malfunction at the press has occurred, check to be sure that the
ready signal is set properly. Remember, for green constant sensors,
the ready signal must be a little shorter than the sensor's actuation
angle. Check that a sensor is actually plugged into this input. Check
connections between remote connection box and controller.
Содержание dipro 1500
Страница 9: ...Table of Contents DiPro 1500 User Manual vi TOC 1092000 ...
Страница 59: ...DiPro 1500 Installation DiPro 1500 User Manual 50 Ch 2 1092000 ...
Страница 77: ...Using DiPro 1500 in Initialization mode DiPro 1500 User Manual 68 Ch 4 1092000 ...
Страница 119: ...DiPro 1500 Fault messages DiPro 1500 User Manual 110 Ch 7 1092000 This page intentionally left blank ...
Страница 125: ......
Страница 126: ......
Страница 127: ......
Страница 128: ......
Страница 129: ......