Cable colour
Kabelfarbe
Kabelfarve
W H
WS
HV
GR
BR
±24VDC WMU 836-1
Single
Open
Auf
Åbn
+
Maintenance
cable
-
±24VDC WMU 836-2/3/4
Synchro
Sy nc
MotorLink™
WMU 836-1/-2/-3/-4
*
ML-
comm
MotorLink™
WMU 836-1/-2/-3-4
ML-comm
WEC / WBC
WLC / WLS
WBS / WSC
WIC xxM
2
M
1
M
24V DC
4
M
3
M
2
M
1
M
WUC xxx
WSC xxx
+/-
-/+
SYNC
24V DC
Maintenance cable
4
M
3
M
SYNC
SYNC
±24V DC Double/Synchro
WMU 836-2/-3/-4
Explanation of words
Worterklärung
Ordforklaring
Maintenance cable
When ±24V DC actuators DO NOT
connect the cable to the control unit. The
cable can be used for maintenance.
Bei ±24V DC Antrieben werden das Kabel
NICHT zu der Stromver-sorgung
angeschlossen. Das Kabel kann in
verbindung mit Service verwendet werden.
Ved ±24V DC motorer tilsluttes kablet
IKKE strømforsyningen. Kablet kan
anvendes ifbm. service.
SYNC
Synchronization communication
Synchronisations-Kommunikation
Synkroniserings-kommunikation
*
Depending on ML-comm
Abhängig von ML-comm
Afhængig af ML-comm
ML-comm
MotorLink™ communication from WEC /
WBC / WLC / WLS / WBS / WSC / WIC
xxM
MotorLink™ Kommunikation mit WEC /
WBC / WLC / WLS / WBS / WSC / WIC xxM
MotorLink™ kommunikation med WEC /
WBC / WLC / WLS / WBS / WSC / WIC
xxM
Maintenance cable
M
WUC xxx
WSC xxx
1
±24V DC Single
WMU 836-1
24V DC
+/-
-/+
Connection of actuators
Verbindung von Antrieben
Sammenkobling af motorer
Für den Anschluss an die Steuereinheit
siehe Steuereinheitanleitung
For connetion to Control Unit
see the Control Unit instruction
For tilslutning til styreenhed
se styreenhedsvejledningen
3. Connection 3. Anschluss 3. Tilslutning
Wiring lenght/dimension
Leitungslänge/-querschnitt
Ledningslængde/-tværsnit
±24V
Single and synchro actuators / Single und Synchro Antriebe / Single og synkr o motorer
Wiring dimensions / Leitungsquersc hnitt / Ledningstvæ rsnit
0,75mm²
1,50 mm²
2,50 mm²
4,00 mm²
Wiring length max.
Leitungslänge max.
Ledningslæ ngde max.
1 actuator / Antrieb / motor
40m
80m
120m
192m
2 actuators / Antriebe / motorer
20m
40m
60m
85m
3 actuators / Antriebe / motorer
13m
27m
40m
64m
4 actuators / Antriebe / motorer
10m
20m
30m
48m
MotorLink™
Single and synchro actuators / Single und Synchro Antriebe / Single og synkro motorer
Wiring dimensions / Leitungsquersc hnitt / Ledningstvæ rsnit
0,75mm²
1,50 mm²
2,50 mm²
4,00 mm²
Wiring length max.
Leitungslänge max.
Ledningslæ ngde max.
1 actuator / Antrieb / motor
40m
50m
2 actuators / Antriebe / motorer
20m
40m
50m
3 actuators / Antriebe / motorer
13m
27m
40m
50m
4 actuators / Antriebe / motorer
10m
20m
30m
48m
Europe
For connection use WindowMaster standard
WLL extention cable (to be ordered seperately).
Other countries
For connection use cables and plugs according
to Nationall Regulations.
Important!
According to national regulation, EN
60204-1 and the directive of machinery, the
yellow-green cable must not be used for
anything else that earth (PE).
If the chain actuator is used in connection with
smoke ventilation, the plugs mounted are to be
cut off, and replaced by plugs/connectors
approved for smoke ventilation.
Permitted voltage drop in the actuator cable
is max. 2V.
When MotorLink™ max. 50m cable.
Der zulässige max. Spannungsabfall auf
der Motorleitung beträgt 2V.
Bei MotorLink™max. 50m Leitung.
Det tilladelige spændingstab på motorled-
ningen må max. være 2V.
Ved MotorLLink™ max. 50m kabel.
Europa
Forlængerkabel WLL kan leveres som
standardvare og skal bestilles separat.
Såfremt kædemotor anvendes i forbindelse
med brandventilation, skal de fabriksmonterede
stik klippes af, og der skal i stedet anvendes
stik/muffer godkendt til brandventilation.
Øvrige lande
For tilslutning anvendes kabler og stik iht. de
gældende nationale regler.
Vigtig!
I henhold til stærkstrømsreglementet,
DS EN 60204-1 og maskindirektivet må den
gulgrønne beskyttelsesleder ikke anvendes til
andet end jord (PE).
Europa
Als eine weiterführende Leitung/Verlängerung ist
eine WLL Standardleitung lieferbar und
gesondert bestellt werden.
Wenn der Ketten-antrieb im Zusammen-hang mit
RWA verwendet werden soll, sind die montierten
Stecker abschneiden, und stattdessen sollen RWA
genehmigte Stecker/Muffen verwendet werden.
Andere Länder
Für den Anschluss müssen Kabel und Stecker
nach die Nationale Richtlinien eingehalten werden.
Wichtig!
Nach den nationalen Vorschriften, EN
60204-1 und der Maschinendirektive, darf die
grün-gelbe Ader zu keinem anderen Zweck als
Erde (PE) verwendet werden.
.
4/12