OPM-133/E

YOURGEN 

The WINCO YourGen meter allows you to see useful 
information about your generator from the front panel 
by displaying RPMs, Voltage, frequency, load, hours, and 
maintenance reminders. It also has the ability to display 
warnings if any parameter gets outside of normal operation 
range. 

Cycle Button (      ) -
During normal operation, the display will toggle through 
on fixed delay. If you want to see any specific item, you 
can press the cycle button to move it to that setting. Once 
the display is selected, the delay before it starts toggling is 
approximately 5 seconds. This button is also used to reset 
maintenance reminders.

RPM - 
The meter will display the RPMs of the engine. This number 
is calculated based upon frequency and is not directly 
measured from the engine. The engine-generator must be 
run at the correct speed in order to produce the proper 
electrical voltage and frequency.

CAUTION: EQUIPMENT DAMAGE

The output voltage should be checked to ensure the 
generator is working properly prior to connecting a 
load to the generator. Failure to do so could result 
in damage to equipment plugged into the unit and 
possible injury to the individual.

OPERATING SPEED 
All engines have a tendency to slow down when a load 
is applied. When the electrical load is connected to the 
generator, the engine is more heavily loaded, and as a 
result, the speed drops slightly. This slight decrease in 
speed, together with the voltage drop  within the generator 
itself, results in a slightly lower voltage when the generator 
is loaded to its full capacity than when running no load. 
The slight variation in speed also affects the frequency 
of the output current. This frequency variation has no 
appreciable effect in the operation of motors, lights, and 
most appliances. However, electronic equipment and clocks 
will be affected if correct RPM is not maintained. See Load 
vs. Output chart.

Although individual units and models vary slightly, the 
normal voltage and frequency of the engine-generator 
described in this manual are approximately as follows, 
under varying loads:

LOAD vs. OUTPUT

Generator 

Load

Speed 

(RPM)

Frequency 

(Hz)

Voltage

120V 

Recpt

240V 

Recpt

None

3690

61.5

125V

258V

Half

3600

60.0

120V

240V

Full

3510

58.5

115V

230V

The speed of the engine was carefully adjusted at the 
factory so that the generator produces the proper voltage 
and frequency. For normal usage, the speed setting should 
not be changed. If the generator is being run continuously 
on a very light load, it is often advisable to lower the 
operating speed slightly. 

The engine will govern itself at full speed. Intentionally 
overriding the governor and operating the generator at 
low voltage may damage both the generator and any load 
connected to it. Running the engine at excessively high 
speeds results in high voltage, which may significantly 
shorten the life of light bulbs and appliances being used, as 
well as possibly damaging the engine.

CAUTION: EQUIPMENT DAMAGE

SPEED ADJUSTMENTS SHOULD ONLY BE MADE BY 
A QUALIFIED SERVICE TECH. Whenever making any 
speed adjustments, check the YourGen meter and be 
sure the voltage and speed are correct.

Output voltage should be checked periodically to ensure 
continued proper operation of the generating plant and 
appliances. 

Hz -
This is the measured frequency of the generator set. See 
the table in the RPM section above for an explanation of 
voltage and frequency ranges under load.

V1 - 
Output voltage of Line 1 (L1 on panel) to neutral. See the 
Load vs. Output table for an explanation of voltage and 
frequency ranges under load. 

V2 - 
Output voltage of Line 2 (L2 on panel) to neutral. See the 
Load vs. Output table for an explanation of voltage and 
frequency ranges under load. 

V1-V2 -
Output voltage of Line 1 (L1) and Line 2 (L2). See the 
Load vs. Output table for an explanation of voltage and 
frequency ranges under load. 

Hours -
This displays the total running hours of the generator set. 
When the generator is turned off, the hours will remain 
displayed. The display is run on a CR2032, ten-year battery. 
Once the unit is running, the battery connected to the unit 
will then supply the power to the YourGen meter.

Load Bars - 
These bars indicate how much load is being used on Line 1 
(L1) and Line 2 (L2).

   

= 1-25%           = 25-50%              = 50-75%               = 75-100%

Содержание W6010DE/I

Страница 1: ...ver need to contact us concerning this unit it will help us to respond to your needs faster MODEL ________________________________________________ SERIAL NUMBER _______________________________________...

Страница 2: ...TROUBLESHOOTING 18 WIRING DIAGRAM 19 CA EVAP EMISSION CONTROL 20 LIMITED WARRANTY 20 SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation an...

Страница 3: ...sent a hazard of possible explosion and or fire A Do not refuel when the engine is running or hot B Keep fuel containers out of reach of children C Do not smoke or use open flame near the generator se...

Страница 4: ...0DE I J 43 21 5 W6010KE 03 A 40 20 GENERATOR Generator Manufacturer Mecc Alte Spa Generator Model Number S16W 130 A Part Number 16346 006 Rotor Resistance 3 95 Ohms Stator Resistance 0 360 Ohms Cap Wi...

Страница 5: ...ED USES DO NOT operate generator where it could get wet or have pooling water near it This generator is NOT weatherproof Failing to keep generator in a dry area may cause an electrical shock resulting...

Страница 6: ...esent the 120 volt output legs of this generator Up to 2 580 watts at 120 volts 43 Amps can be drawn from the receptacles attached to either A or B output legs This generator is capable of producing 2...

Страница 7: ...evel be sure you properly tighten the oil fill cap NOTE This engine generator must be on a level surface before you check or add oil to the system The necessity of using the correct oil and keeping th...

Страница 8: ...ry presents a risk of electrical shock and high short circuit current The following precautions must be observed when working with batteries 1 Remove watches rings and other metal objects 2 Use tools...

Страница 9: ...as a battery charging circuit to recharge dead batteries LIFTING EYE INSTALLATION In the bag of parts for the lifting eye ensure all of the required materials are included 2 qty 5 16 18 x 2 25 button...

Страница 10: ...osition The lever is located under the key switch as pictured 3 Turn key to 1st position Ref A 4 Turn key to the 2nd position starting Ref B A B 5 Return key to 1st position when engine is running Ref...

Страница 11: ...revent damage to either the receptacles or the generator The generator is a limited source of electrical power therefore pay special attention to the receptacle and generator ratings The nameplate rat...

Страница 12: ...stored while the generator is connected This generator is GFCI protected so the transfer switch needs to be GFCI compatible If the transfer switch is not GFCI compatible the breaker on the generator w...

Страница 13: ...ual are approximately as follows under varying loads LOAD vs OUTPUT Generator Load Speed RPM Frequency Hz Voltage 120V Recpt 240V Recpt None 3690 61 5 125V 258V Half 3600 60 0 120V 240V Full 3510 58 5...

Страница 14: ...s generator is capable of producing 21 5 Amps of 240 volt current at C Check the appliance or tool nameplates for the current and voltage to insure compatibility Remember that power taken from C reduc...

Страница 15: ...Check dry air cleaner Fuel tank cleaning Clean cooling fins Replace engine oil Replace oil filter Replace fuel filter Set and clean injectors Rocker arm adjustment Drain Bolt C Replace oil drain plug...

Страница 16: ...is excessively dirty replace with a new filter You can use pressurized air not to exceed 30 psi to clean the filter Always blow the compressed air from inside to the outside F Clean the dirt from the...

Страница 17: ...ubrication B Receptacles Quality receptacles have been utilized If a receptacle should become cracked or otherwise damaged replace it Using damaged or cracked receptacles can be both dangerous to the...

Страница 18: ...uit breaker trips Defective load Defective receptacle Excessive load GFCI type of load i e a building with bonded neutral Voltage too high Engine speed is too high Generator overheating Overloaded Ins...

Страница 19: ...19 OPM 133 E WIRING DIAGRAM...

Страница 20: ...nd Purchaser s sole remedy for a failure under this warranty shall be limited to the repair of the product At WINCO s option material found to be defective in material or workmanship under normal use...

Отзывы: