background image

16

OPM-133/E

B. Remove the wing nut.

  C. Remove the filter element.

  D. Check the rubber seal is undamaged.

  E. To loosen debris, gently tap the air filter on a hard 
    surface. If the air filter is excessively dirty replace with a 
    new filter. You can use pressurized air (not to exceed 
    30 psi) to clean the filter. Always blow the compressed 
    air from inside to the outside.
  F. Clean the dirt from the inside of the air cleaner body 
    and cover. Reinstall the filter in housing. Tighten the 
    wing nut securely.
  G. Install and secure the cover.
  H. Remove and clean the pre-filter if clogged.

Содержание W6010DE/I

Страница 1: ...ver need to contact us concerning this unit it will help us to respond to your needs faster MODEL ________________________________________________ SERIAL NUMBER _______________________________________...

Страница 2: ...TROUBLESHOOTING 18 WIRING DIAGRAM 19 CA EVAP EMISSION CONTROL 20 LIMITED WARRANTY 20 SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation an...

Страница 3: ...sent a hazard of possible explosion and or fire A Do not refuel when the engine is running or hot B Keep fuel containers out of reach of children C Do not smoke or use open flame near the generator se...

Страница 4: ...0DE I J 43 21 5 W6010KE 03 A 40 20 GENERATOR Generator Manufacturer Mecc Alte Spa Generator Model Number S16W 130 A Part Number 16346 006 Rotor Resistance 3 95 Ohms Stator Resistance 0 360 Ohms Cap Wi...

Страница 5: ...ED USES DO NOT operate generator where it could get wet or have pooling water near it This generator is NOT weatherproof Failing to keep generator in a dry area may cause an electrical shock resulting...

Страница 6: ...esent the 120 volt output legs of this generator Up to 2 580 watts at 120 volts 43 Amps can be drawn from the receptacles attached to either A or B output legs This generator is capable of producing 2...

Страница 7: ...evel be sure you properly tighten the oil fill cap NOTE This engine generator must be on a level surface before you check or add oil to the system The necessity of using the correct oil and keeping th...

Страница 8: ...ry presents a risk of electrical shock and high short circuit current The following precautions must be observed when working with batteries 1 Remove watches rings and other metal objects 2 Use tools...

Страница 9: ...as a battery charging circuit to recharge dead batteries LIFTING EYE INSTALLATION In the bag of parts for the lifting eye ensure all of the required materials are included 2 qty 5 16 18 x 2 25 button...

Страница 10: ...osition The lever is located under the key switch as pictured 3 Turn key to 1st position Ref A 4 Turn key to the 2nd position starting Ref B A B 5 Return key to 1st position when engine is running Ref...

Страница 11: ...revent damage to either the receptacles or the generator The generator is a limited source of electrical power therefore pay special attention to the receptacle and generator ratings The nameplate rat...

Страница 12: ...stored while the generator is connected This generator is GFCI protected so the transfer switch needs to be GFCI compatible If the transfer switch is not GFCI compatible the breaker on the generator w...

Страница 13: ...ual are approximately as follows under varying loads LOAD vs OUTPUT Generator Load Speed RPM Frequency Hz Voltage 120V Recpt 240V Recpt None 3690 61 5 125V 258V Half 3600 60 0 120V 240V Full 3510 58 5...

Страница 14: ...s generator is capable of producing 21 5 Amps of 240 volt current at C Check the appliance or tool nameplates for the current and voltage to insure compatibility Remember that power taken from C reduc...

Страница 15: ...Check dry air cleaner Fuel tank cleaning Clean cooling fins Replace engine oil Replace oil filter Replace fuel filter Set and clean injectors Rocker arm adjustment Drain Bolt C Replace oil drain plug...

Страница 16: ...is excessively dirty replace with a new filter You can use pressurized air not to exceed 30 psi to clean the filter Always blow the compressed air from inside to the outside F Clean the dirt from the...

Страница 17: ...ubrication B Receptacles Quality receptacles have been utilized If a receptacle should become cracked or otherwise damaged replace it Using damaged or cracked receptacles can be both dangerous to the...

Страница 18: ...uit breaker trips Defective load Defective receptacle Excessive load GFCI type of load i e a building with bonded neutral Voltage too high Engine speed is too high Generator overheating Overloaded Ins...

Страница 19: ...19 OPM 133 E WIRING DIAGRAM...

Страница 20: ...nd Purchaser s sole remedy for a failure under this warranty shall be limited to the repair of the product At WINCO s option material found to be defective in material or workmanship under normal use...

Отзывы: