Winco PSS12H2E Скачать руководство пользователя страница 7

7

REV F

60706-209

 LP TANK SIZING

Tank Temperature

Tank Size

60° F (16° C)

150 Gallons

32° F (0° C)

250 Gallons

0° F (18° C)

500 Gallons

-20° F (-29° C)

1000 Gallons

NATURAL GAS (NG)

The primary regulator (fuel meter) on the building should deliver the 

correct volume and pressure to the generator set. This regulator must 

be sized to deliver the required BTU’s to the generator set and all other 

appliances in the building. If the primary regulator (fuel meter) is a high 

pressure regulator, then a low pressure regulator must be installed 

to bring the pressure down to 4-6 oz. (7-11 inches water column) of 

pressure. This low pressure regulator must be at least 10 feet from the 

engine generator set; any closer installation will require a larger line 

be installed to provide a fuel reservoir. If this is not done, the demand 

regulator on the unit and the pressure regulator in the fuel line will 

interfere with each other. This regulator must be sized to accommodate 

the demand of the generator set and any other appliance connected to 

it. See the following table for the correct size of pipe to be installed.

Feet*

Size of pipe

Up to 25 ft

¾” pipe

25 - 100 ft

1” pipe

Over 100 ft

Use a two regulator system

*Allow an additional 3 feet for each standard elbow. DO NOT use 

‘street ells’ (restrictive).

WARNING: PERSONAL DANGER:  

Do not use galvanized pipe in fuel line runs. The galvanized coating 

can become eroded and flake off, causing possible obstructions in the 

regulator or fuel valve. The results could range from inoperative engine 

to hazardous fuel leaks.

CAUTION:

Be careful when sealing gas joints. Excessive sealing compound can 

be drawn into the solenoid, regulator or carburetor causing an engine 

malfunction.

FUEL PRESSURE

Correct fuel pressure cannot be stressed enough. The most common 

cause for inoperative systems is an inadequate or incorrect fuel 

pressure. Performance of the engine is in direct relation to the 

correctness of the fuel system. Shown below is a diagram of a typical 

LP vapor fuel installation. Notice the following tables give two different 

units of measuring fuel pressure. The first and most accurate is the 

use of a simple water manometer. A manometer is calibrated in inches 

of water column . The second is with a pressure gauge calibrated in 

ounces per square inch. 

WARNING: FIRE HAZARD:

All fuel runs should be installed by a licensed fuel supplier.

To connect the fuel line to the generator set you will connect your 

incoming fuel line to the 3/4 inch NPT fitting located on the left side 

of the engine-generator set. This fitting is shipped with a plastic plug 

installed to insure the fuel system stays clean. For all vapor fuel 

systems the delivery pressure of the fuel to the fuel solenoid on the unit 

must be four to six ounces psi (per square inch) or 7 to 11 inches

W.C. (water column). These fuel pressures are critical; failure to 

provide the proper pressure can cause many problems ranging from a 

unit that will not start to causing damage to the fuel system.

These units are normally tested on Natural Gas and will have a 

tag hanging on the fuel hose indicating on what fuel your unit was 

factory tested. If you are running on LP or have to change fuel types 

at any time, see information on page 8 on NG/LP CONVERSION. 

INSTALLING THE FUEL LINE

NOTICE:

 The engine generator sets are properly adjusted before they 

leave the factory. A tag is attached to the unit that specifies the fuel, 

natural gas (NG) or propane vapor (LP) that the unit was set up and 

tested on.

NATURAL GAS or LP VAPOR PIPE SIZE

Size of pipe normally required for generators operating on natural gas 

or LP vapor. Unit location will determine the size of fuel line that is 

required to supply the engine with a constant fuel pressure and volume.

LIQUID PROPANE VAPOR (LP)

Refer to the tables on the following pages for fuel line size and 

recommended tank size. For distances of 100 feet or over, a two 

regulator fuel system is recommended. This is accomplished by 

installing a primary regulator at the tank which will reduce the tank 

pressure down to 10 to 15 lbs. A low pressure regulator is installed to 

further reduce the fuel pressure to the required four (4) to six (6) oz. 

operating pressure. This low pressure regulator must be at least 10 

feet from the engine generator set; any closer installation will require 

a larger line be installed to provide a fuel reservoir. This is also true 

for the single low pressure regulator, it should also be a minimum of 

10 feet from the unit. If this is not done, the demand regulator on the 

unit and the pressure regulator in the fuel line will interfere with each 

other. When the two (2) regulator system is used on LP, a fuel line size 

of 1/2 to 5/8 inch is generally adequate for distances up to 300 feet 

from the primary to the low pressure regulator. Consult your local fuel 

supplier for your exact requirements . The appropriate line size from 

the following table is then installed from the low pressure regulator to 

the generator set.

Feet*

Size of pipe

Up to 25 ft

¾” pipe

25 - 100 ft

1” pipe

Over 100 ft

Use a two regulator system

*Allow an additional 3 feet for each standard elbow. DO NOT use 

‘street ells’ (restrictive).

Содержание PSS12H2E

Страница 1: ...WINCO INC 225 S CORDOVA AVE LE CENTER MN 56057 507 357 6821 SERVICE DEPT 507 357 6831 www wincogen com INSTALLATION AND OPERATORS PSS12H2W E F GENERATOR MANUAL...

Страница 2: ...GER SOLAR CHARGER OPTION 10 AC ELECTRICAL CONNECTIONS 11 GENERATOR CONNECTIONS WINCO UL ATS ASCO 185 DC ELECTRICAL INTERCONNECTION 12 ASCO 185 UL SWITCH INITIAL START UP 12 START UP PROCEDURE CUSTOMER...

Страница 3: ...xpect from WINCO should you need service assistance in the future COPY YOUR MODEL AND SERIAL NUMBER HERE No other WINCO generator has the same serial number as yours If you should ever need to contact...

Страница 4: ...the earth 2 FIRE HAZARD Gasoline and other fuels present a hazard of possible explosion and or fire A Do not refuel when the engine is running or hot B Keep fuel containers out of reach of children C...

Страница 5: ...recommended The transfer switch is UL1008 approved A fourteen day electronic exerciser circuit is installed in the ATS as standard equipment The ATS also contains the power failure sensing circuitry...

Страница 6: ...isfactory system installation The information in this manual is offered only as a guide to finalizing your installation plans ENGINE GENERATOR SET MOUNTING WARNING PERSONAL INJURY The enclosures on th...

Страница 7: ...ng located on the left side of the engine generator set This fitting is shipped with a plastic plug installed to insure the fuel system stays clean For all vapor fuel systems the delivery pressure of...

Страница 8: ...load Line PSI 10 15 lbs 7 11 in 4 6 oz 7 11 in 4 6 oz Full load Line PSI 10 15 lbs 7 11 in 4 6 oz 7 11 in 4 6 oz Natural gas Ref 2 3 4 Unit off 2 PSI 7 11 in 4 6 oz 7 11 in 4 6 oz Starting 2 PSI 7 11...

Страница 9: ...charger has an indicator light on it Red indicates it is charging and green indicates it is in storage mode float charge This charger is INSTALLING THE BATTERY CAUTION In the following battery install...

Страница 10: ...not intended to recharge a battery which has become completely discharged It is designed to produce enough current to recharge a slightly low battery and maintain a fully charged battery SOLAR CHARGER...

Страница 11: ...ed emergency distribution panel must be installed All selected emergency circuits are removed from main distribution panels and reinstalled in the emergency distribution panel Suggested circuits freez...

Страница 12: ...GRZQ OHDUDQFH IRU VHUYLFH DQG PDLQWHQDQFH RQ DOO VLGHV 3URSHU IXHO OLQH PDWHULDO DQG VL H OO IXHO OLQH FRQQHFWLRQV WLJKW XHO OLQH SURWHFWHG DQG D PRLVWXUH WUDS LQVWDOOHG PD EH required for NG 3 1 SUH...

Страница 13: ...DAMAGE SPEED ADJUSTMENTS SHOULD ONLY BE MADE BY A QUALIFIED SERVICE TECH NOTICE If for any reason during the check out procedures the Voltage and frequency are not correct press the red Stop Reset but...

Страница 14: ...utton to cancel the active time delay or exercise period stops the generator after cool down SET ENGINE EXERCISER Use this button to set the automatic exerciser INDICATOR LIGHTS On the front control d...

Страница 15: ...ITY LINE TO POWER BATTERY TENDER AND OPTIONAL ENGINE HEATER CUSTOMER GENERATOR OUTPUT CONNECTIONS TO EMERGENCY TRANSFER SWITCH EMERGENCY STOP CONTACTS PROVIDED FOR REMOTE EMERGENCY STOP SWITCH UNIT WI...

Страница 16: ...16 REV F 60706 209 SEQUENCE OF OPERATION UTILITY FAILURE...

Страница 17: ...CODES Auxiliary inputs can be user configured and will display he message as written by the user Fail to Start The engine has not fired after the preset number of start attempts Fail to Stop The modu...

Страница 18: ...ENTATIVE MAINTENANCE Reasonable care in preventative maintenance will ensure high reliability and a long life for the engine generator set and Automatic Transfer Switch WARNING When performing any typ...

Страница 19: ...8 Locked up engine generator set 9 Defective starter fuel solenoid relays ENGINE CRANKS BUT WILL NOT START 1 Improper fuel pressure being delivered to unit 2 Fuel supply shut off 3 Fuel supply empty...

Страница 20: ...20 REV F 60706 209 PAD LAYOUT DRAWING 21 11075 01 60706 209 ENGINE GENERATOR SET PAD LAYOUT...

Страница 21: ...TIONS ASCO 165 SERIES TRANSFER SWITCH 9 8 7 6 5 4 3 2 1 TB7 L6 NEUTRAL T B 4 3 2 1 L2 GROUND T B 9 POSITION CONNECTOR G1 N G3 GND N L1 GND 1 5 24 23 ES ES 2 4 1 24 22 1 23 CONTROL TOWER ENGINE CONTROL...

Страница 22: ...22 REV F 60706 209 SOLAR CONTROL PANEL IF EQUIPPED EXTERNAL RECEPTACLE ASSEMBLY IF EQUIPPED N N GND GND G1 G1 G3 G3 G3 G3...

Страница 23: ...23 REV F 60706 209 SOLAR PANEL ASSEMBLY IF EQUIPPED...

Страница 24: ...nd fitness for a particular purpose are limited to 12 months or 1000 hours which ever occurs first from date of purchase In no event is WINCO liable for incidental or consequential damages Note Some s...

Отзывы: