INITIAL START UP

WARNING:

DO NOT jump start these engine generator sets. Starting these units 

on a low battery of jump starting them will cause damage to the engine 

control module.

Use the following checklist to verify correct installation before starting 

the engine:

 

□ Engine oil.* Check level & fill as required with proper 

   grade/quantity.

 

□ Unit mounting base properly bolted down.

 

□ Clearance for service and maintenance on all sides.

 

□ Proper fuel line material and size.

 

□ All fuel line connections tight. 

 

□ Fuel line protected and a moisture trap installed (may be 

 

  required for NG).

 

□ LP/NG pressure OK. 4-6 oz. (7-11 in. WC).

 

□ Battery connections clean and tight.

 

□ Battery fully charged. 

 

□ All AC and DC wiring installed and properly protected.

* Refer to engine owners manual for proper levels and types.

After completing the above checklist, the engine generator set is ready 

for the initial start-up test.

START UP PROCEDURE

ENGINE-GENERATOR SET ONLY

The engine control module (ECM) is manufactured by Deep Sea 

Electronics. Model 3110 is used on this generator set. 

See following picture and look for more information stated within this 

manual.

MANUAL OPERATION

Press and release the red Stop/Reset button. Then press and release 

the green Start Engine button. The engine-generator will crank and 

start automatically. If the engine fails to start, reference the fault codes 

to correct the problem before proceeding.

10

REV B

60706-229

DC ELECTRICAL INTERCONNECTION

CAUTION:

Never run the AC and DC wiring on the same conduit.

ASCO 185 UL SWITCH

Your DC connection points in the ASCO 185 UL ATS are on the 

terminal block on the bottom of the controller in the lower left hand 

corner of the ATS panel. The terminal block (TB7) is numbered 1 

through 9. These terminals will accept # 22 - # 14 AWG stranded wire. 

It is recommended that you use # 16 AWG for distances up to 200 

feet. You need to run two (2) wires from the engine generator set to the 

transfer switch. You will be using terminals 4 and 5, wire Start # 23 will 

connect to terminal # 5 and wire Battery Negative # 1 will connect to 

terminal # 4. See the following table and illustration.

Wire #

Purpose

Recommended Color

#23

Start

Black

#1

Battery negative

White

INITIAL START UP

WARNING:

DO NOT jump start these engine generator sets. Starting these units 

on a low battery of jump starting them will cause damage to the engine 

control module.

Use the following checklist to verify correct installation before starting 

the engine:

Ƒ(QJLQHRLO&KHFNOHYHO ¿OODVUHTXLUHGZLWKSURSHU

   grade/quantity.

Ƒ8QLWPRXQWLQJEDVHSURSHUO\EROWHGGRZQ

Ƒ&OHDUDQFHIRUVHUYLFHDQGPDLQWHQDQFHRQDOOVLGHV

Ƒ3URSHUIXHOOLQHPDWHULDODQGVL]H

Ƒ$OOIXHOOLQHFRQQHFWLRQVWLJKW

Ƒ)XHOOLQHSURWHFWHGDQGDPRLVWXUHWUDSLQVWDOOHGPD\EH

 

  required for NG).

Ƒ/31*SUHVVXUH2.R]LQ:&

Ƒ%DWWHU\FRQQHFWLRQVFOHDQDQGWLJKW

Ƒ%DWWHU\IXOO\FKDUJHG

Ƒ$OO$&DQG'&ZLULQJLQVWDOOHGDQGSURSHUO\SURWHFWHG

* Refer to engine owners manual for proper levels and types.

After completing the above checklist, the engine generator set is ready 

for the initial start-up test.

START UP PROCEDURE

ENGINE-GENERATOR SET ONLY

The engine control module (ECM) is manufactured by Deep Sea 

Electronics. Model 3110 is used on this generator set. 

See following picture and look for more information stated within this 

manual.

MANUAL OPERATION

Press and release the red Stop/Reset button. Then press and release 

the green Start Engine button. The engine-generator will crank and 

start automatically. If the engine fails to start, reference the fault codes 

to correct the problem before proceeding.

generator under load. Should you ever have to work on the switch, 

you will be able to disconnect the power and work on the switch cold 

without having the power company pull your meter.

7RZLUHWKHDXWRPDWLFWUDQVIHUVZLWFKLQWRWKHH[LVWLQJZLULQJ¿UVW

determine which circuits will be on the emergency load circuit. If the 

entire load is to be transferred, the transfer switch can be wired in 

directly after the watt-hour meter and the service entrance, providing 

WKHVHUYLFHHQWUDQFHDPSHUHUDWLQJLVZLWKLQWKHWUDQVIHUVZLWFK¶VUDWHG

capability. 

,IRQO\VSHFL¿FFLUFXLWVDUHWREHSRZHUHGXQGHUHPHUJHQF\SRZHU

failure conditions, an additional distribution panel designated 

“emergency distribution panel” must be installed.

All selected emergency circuits are removed from main distribution 

panels and reinstalled in the emergency distribution panel. Suggested 

circuits: freezer, refrigerator, furnace, emergency lights, sump pump, 

emergency outlet circuits, etc. Total running load must not exceed 

generator rating.

DC ELECTRICAL INTERCONNECTION

CAUTION:

Never run the AC and DC wiring on the same conduit.

ASCO 185 UL SWITCH

Your DC connection points in the ASCO 185 UL ATS are on the 

terminal block on the bottom of the controller in the lower left hand 

corner of the ATS panel. The terminal block (TB7) is numbered 1 

through 9. These terminals will accept # 22 - # 14 AWG stranded wire. 

It is recommended that you use # 16 AWG for distances up to 200 

feet. You need to run two (2) wires from the engine generator set to the 

transfer switch. You will be using terminals 4 and 5, wire Start # 23 will 

connect to terminal # 5 and wire Battery Negative # 1 will connect to 

terminal # 4. See the following table and illustration.

Wire #

Purpose

Recommended Color

#23

Start

Black

#1

Battery negative

White

Содержание PSS12H2E

Страница 1: ...WINCO INC 225 S CORDOVA AVE LE CENTER MN 56057 507 357 6821 SERVICE DEPT 507 357 6831 www wincogen com INSTALLATION AND OPERATORS PSS12H2W E F GENERATOR MANUAL...

Страница 2: ...GER SOLAR CHARGER OPTION 10 AC ELECTRICAL CONNECTIONS 11 GENERATOR CONNECTIONS WINCO UL ATS ASCO 185 DC ELECTRICAL INTERCONNECTION 12 ASCO 185 UL SWITCH INITIAL START UP 12 START UP PROCEDURE CUSTOMER...

Страница 3: ...xpect from WINCO should you need service assistance in the future COPY YOUR MODEL AND SERIAL NUMBER HERE No other WINCO generator has the same serial number as yours If you should ever need to contact...

Страница 4: ...the earth 2 FIRE HAZARD Gasoline and other fuels present a hazard of possible explosion and or fire A Do not refuel when the engine is running or hot B Keep fuel containers out of reach of children C...

Страница 5: ...recommended The transfer switch is UL1008 approved A fourteen day electronic exerciser circuit is installed in the ATS as standard equipment The ATS also contains the power failure sensing circuitry...

Страница 6: ...isfactory system installation The information in this manual is offered only as a guide to finalizing your installation plans ENGINE GENERATOR SET MOUNTING WARNING PERSONAL INJURY The enclosures on th...

Страница 7: ...ng located on the left side of the engine generator set This fitting is shipped with a plastic plug installed to insure the fuel system stays clean For all vapor fuel systems the delivery pressure of...

Страница 8: ...load Line PSI 10 15 lbs 7 11 in 4 6 oz 7 11 in 4 6 oz Full load Line PSI 10 15 lbs 7 11 in 4 6 oz 7 11 in 4 6 oz Natural gas Ref 2 3 4 Unit off 2 PSI 7 11 in 4 6 oz 7 11 in 4 6 oz Starting 2 PSI 7 11...

Страница 9: ...charger has an indicator light on it Red indicates it is charging and green indicates it is in storage mode float charge This charger is INSTALLING THE BATTERY CAUTION In the following battery install...

Страница 10: ...not intended to recharge a battery which has become completely discharged It is designed to produce enough current to recharge a slightly low battery and maintain a fully charged battery SOLAR CHARGER...

Страница 11: ...ed emergency distribution panel must be installed All selected emergency circuits are removed from main distribution panels and reinstalled in the emergency distribution panel Suggested circuits freez...

Страница 12: ...GRZQ OHDUDQFH IRU VHUYLFH DQG PDLQWHQDQFH RQ DOO VLGHV 3URSHU IXHO OLQH PDWHULDO DQG VL H OO IXHO OLQH FRQQHFWLRQV WLJKW XHO OLQH SURWHFWHG DQG D PRLVWXUH WUDS LQVWDOOHG PD EH required for NG 3 1 SUH...

Страница 13: ...DAMAGE SPEED ADJUSTMENTS SHOULD ONLY BE MADE BY A QUALIFIED SERVICE TECH NOTICE If for any reason during the check out procedures the Voltage and frequency are not correct press the red Stop Reset but...

Страница 14: ...utton to cancel the active time delay or exercise period stops the generator after cool down SET ENGINE EXERCISER Use this button to set the automatic exerciser INDICATOR LIGHTS On the front control d...

Страница 15: ...ITY LINE TO POWER BATTERY TENDER AND OPTIONAL ENGINE HEATER CUSTOMER GENERATOR OUTPUT CONNECTIONS TO EMERGENCY TRANSFER SWITCH EMERGENCY STOP CONTACTS PROVIDED FOR REMOTE EMERGENCY STOP SWITCH UNIT WI...

Страница 16: ...16 REV F 60706 209 SEQUENCE OF OPERATION UTILITY FAILURE...

Страница 17: ...CODES Auxiliary inputs can be user configured and will display he message as written by the user Fail to Start The engine has not fired after the preset number of start attempts Fail to Stop The modu...

Страница 18: ...ENTATIVE MAINTENANCE Reasonable care in preventative maintenance will ensure high reliability and a long life for the engine generator set and Automatic Transfer Switch WARNING When performing any typ...

Страница 19: ...8 Locked up engine generator set 9 Defective starter fuel solenoid relays ENGINE CRANKS BUT WILL NOT START 1 Improper fuel pressure being delivered to unit 2 Fuel supply shut off 3 Fuel supply empty...

Страница 20: ...20 REV F 60706 209 PAD LAYOUT DRAWING 21 11075 01 60706 209 ENGINE GENERATOR SET PAD LAYOUT...

Страница 21: ...TIONS ASCO 165 SERIES TRANSFER SWITCH 9 8 7 6 5 4 3 2 1 TB7 L6 NEUTRAL T B 4 3 2 1 L2 GROUND T B 9 POSITION CONNECTOR G1 N G3 GND N L1 GND 1 5 24 23 ES ES 2 4 1 24 22 1 23 CONTROL TOWER ENGINE CONTROL...

Страница 22: ...22 REV F 60706 209 SOLAR CONTROL PANEL IF EQUIPPED EXTERNAL RECEPTACLE ASSEMBLY IF EQUIPPED N N GND GND G1 G1 G3 G3 G3 G3...

Страница 23: ...23 REV F 60706 209 SOLAR PANEL ASSEMBLY IF EQUIPPED...

Страница 24: ...nd fitness for a particular purpose are limited to 12 months or 1000 hours which ever occurs first from date of purchase In no event is WINCO liable for incidental or consequential damages Note Some s...

Отзывы: