SPECIFICATIONS

GENERATOR

Fuel

Watts*

Volts

Amps

HZ 

PH

RPM

LP

12,000

120/240 50

60

1

3600

NG

10,000

120/240 41

60

1

3600

*Continuous rating.

Derate 3.5% per 1000 feet elevation above sea level.

FUEL CONSUMPTION

Natural Gas

1000 BTU/FT³

LP Vapor

2520 BTU/FT³

CF/HR*

194

75.4

BTU/HR*

194,000

190,000

GAL/HR*

N/A

2.1

*Based on full load operation.

LP TANK SIZING

Tank Temperature

Tank Size

60° F (16° C)

150 Gallons

32° F (0° C)

250 Gallons

0° F (18° C)

500 Gallons

-20° F (-29° C)

1000 Gallons

ENGINE

Make    Honda 

Model    GX690

Displacement 

  688 

CC/OHV

Cylinders/Sleeves   

V-Twin/Cast Iron

Ignition 

   Electronic

Governor 

   Mechanical

Exhaust 

   Critical 

Grade, 

Glass-pack

See engine manual for additional information

INTRODUCTION

PRODUCT DESCRIPTION

The package standby system is designed to automatically provide 

standby power to unattended loads during electrical outages. Upon 

interruption of normal electrical service, the packaged standby system 

electrical control circuits will automatically start the engine. The 

generator will produce electrical power and the Automatic Transfer 

Switch (ATS) will automatically transfer the electrical loads to the

engine-generator set. Upon restoration of normal electrical service the 

emergency transfer switch will sense return of the normal commercial 

power. The Automatic Transfer Switch will transfer the load back

to the normal commercial power source. The engine control circuits will 

begin a cool-down cycle, after which the fuel supply will be shut off and 

the engine ignition system disabled.

AUTOMATIC TRANSFER SWITCH (not included)

A wall mounted ASCO 185 Automatic Transfer Switch (ATS) designed 

for inside or outside installation is recommended. The transfer switch is 

UL1008 approved. A fourteen day electronic exerciser circuit is installed

in the ATS as standard equipment. The ATS also contains the power 

failure sensing circuitry necessary to start and stop the engine 

generator set. The transfer switch is also equipped standard with a 3 

second start delay, and a 15 second transfer delay to allow the engine 

to warm up before transferring the load to the generator. When the line 

power is restored the ATS has a 5 minute transfer delay to allow the 

incoming utility to stabilize before transferring back to line power and 

then an additional 1 minute engine cool down delay before the engine 

shuts down. Read and understand the ATS owners manual before 

installing, servicing or operating the transfer switch.

UL Automatic Transfer Switch Sizes 

UNIT 

    LINE 

SIDE    

GENERATOR

     CONTACTOR 

   

SIDE 

CONTACTOR

ULPSS12H2W  

 

100-400 AMPS    

100-400 AMPS

The ASCO185 100-400 Amp Switches are available in single phase 

only.

ENGINE / GENERATOR

The engine generator set consists of a Honda GX690, twin cylinder, 

four cycle air cooled engine. The engine is factory equipped to run 

on LP or NG fuel. The engine operates at 3600 rpm and frequency 

regulation is maintained by the engine governor within 4 cycles 

variation (62.5 Hz - 58.5 Hz) from no load to rated load. The generator 

is a brushless, single bearing, direct drive, rotating field design. The 

generator is connected to the engine’s tapered (quill) crankshaft 

extension. The engine generator is mounted in a drip-proof enclosure 

for outside installation. Connection boxes and terminal blocks are 

provided for all customer connections (both AC output and DC control). 

A customer supplied 12 volt 500 CCA (BCI group 26) battery is required 

to complete the installation. 

NOTICE: 

This unit will automatically transfer if a power outage occurs while 

running in an exercise mode.

Содержание PSS12H2E

Страница 1: ...WINCO INC 225 S CORDOVA AVE LE CENTER MN 56057 507 357 6821 SERVICE DEPT 507 357 6831 www wincogen com INSTALLATION AND OPERATORS PSS12H2W E F GENERATOR MANUAL...

Страница 2: ...GER SOLAR CHARGER OPTION 10 AC ELECTRICAL CONNECTIONS 11 GENERATOR CONNECTIONS WINCO UL ATS ASCO 185 DC ELECTRICAL INTERCONNECTION 12 ASCO 185 UL SWITCH INITIAL START UP 12 START UP PROCEDURE CUSTOMER...

Страница 3: ...xpect from WINCO should you need service assistance in the future COPY YOUR MODEL AND SERIAL NUMBER HERE No other WINCO generator has the same serial number as yours If you should ever need to contact...

Страница 4: ...the earth 2 FIRE HAZARD Gasoline and other fuels present a hazard of possible explosion and or fire A Do not refuel when the engine is running or hot B Keep fuel containers out of reach of children C...

Страница 5: ...recommended The transfer switch is UL1008 approved A fourteen day electronic exerciser circuit is installed in the ATS as standard equipment The ATS also contains the power failure sensing circuitry...

Страница 6: ...isfactory system installation The information in this manual is offered only as a guide to finalizing your installation plans ENGINE GENERATOR SET MOUNTING WARNING PERSONAL INJURY The enclosures on th...

Страница 7: ...ng located on the left side of the engine generator set This fitting is shipped with a plastic plug installed to insure the fuel system stays clean For all vapor fuel systems the delivery pressure of...

Страница 8: ...load Line PSI 10 15 lbs 7 11 in 4 6 oz 7 11 in 4 6 oz Full load Line PSI 10 15 lbs 7 11 in 4 6 oz 7 11 in 4 6 oz Natural gas Ref 2 3 4 Unit off 2 PSI 7 11 in 4 6 oz 7 11 in 4 6 oz Starting 2 PSI 7 11...

Страница 9: ...charger has an indicator light on it Red indicates it is charging and green indicates it is in storage mode float charge This charger is INSTALLING THE BATTERY CAUTION In the following battery install...

Страница 10: ...not intended to recharge a battery which has become completely discharged It is designed to produce enough current to recharge a slightly low battery and maintain a fully charged battery SOLAR CHARGER...

Страница 11: ...ed emergency distribution panel must be installed All selected emergency circuits are removed from main distribution panels and reinstalled in the emergency distribution panel Suggested circuits freez...

Страница 12: ...GRZQ OHDUDQFH IRU VHUYLFH DQG PDLQWHQDQFH RQ DOO VLGHV 3URSHU IXHO OLQH PDWHULDO DQG VL H OO IXHO OLQH FRQQHFWLRQV WLJKW XHO OLQH SURWHFWHG DQG D PRLVWXUH WUDS LQVWDOOHG PD EH required for NG 3 1 SUH...

Страница 13: ...DAMAGE SPEED ADJUSTMENTS SHOULD ONLY BE MADE BY A QUALIFIED SERVICE TECH NOTICE If for any reason during the check out procedures the Voltage and frequency are not correct press the red Stop Reset but...

Страница 14: ...utton to cancel the active time delay or exercise period stops the generator after cool down SET ENGINE EXERCISER Use this button to set the automatic exerciser INDICATOR LIGHTS On the front control d...

Страница 15: ...ITY LINE TO POWER BATTERY TENDER AND OPTIONAL ENGINE HEATER CUSTOMER GENERATOR OUTPUT CONNECTIONS TO EMERGENCY TRANSFER SWITCH EMERGENCY STOP CONTACTS PROVIDED FOR REMOTE EMERGENCY STOP SWITCH UNIT WI...

Страница 16: ...16 REV F 60706 209 SEQUENCE OF OPERATION UTILITY FAILURE...

Страница 17: ...CODES Auxiliary inputs can be user configured and will display he message as written by the user Fail to Start The engine has not fired after the preset number of start attempts Fail to Stop The modu...

Страница 18: ...ENTATIVE MAINTENANCE Reasonable care in preventative maintenance will ensure high reliability and a long life for the engine generator set and Automatic Transfer Switch WARNING When performing any typ...

Страница 19: ...8 Locked up engine generator set 9 Defective starter fuel solenoid relays ENGINE CRANKS BUT WILL NOT START 1 Improper fuel pressure being delivered to unit 2 Fuel supply shut off 3 Fuel supply empty...

Страница 20: ...20 REV F 60706 209 PAD LAYOUT DRAWING 21 11075 01 60706 209 ENGINE GENERATOR SET PAD LAYOUT...

Страница 21: ...TIONS ASCO 165 SERIES TRANSFER SWITCH 9 8 7 6 5 4 3 2 1 TB7 L6 NEUTRAL T B 4 3 2 1 L2 GROUND T B 9 POSITION CONNECTOR G1 N G3 GND N L1 GND 1 5 24 23 ES ES 2 4 1 24 22 1 23 CONTROL TOWER ENGINE CONTROL...

Страница 22: ...22 REV F 60706 209 SOLAR CONTROL PANEL IF EQUIPPED EXTERNAL RECEPTACLE ASSEMBLY IF EQUIPPED N N GND GND G1 G1 G3 G3 G3 G3...

Страница 23: ...23 REV F 60706 209 SOLAR PANEL ASSEMBLY IF EQUIPPED...

Страница 24: ...nd fitness for a particular purpose are limited to 12 months or 1000 hours which ever occurs first from date of purchase In no event is WINCO liable for incidental or consequential damages Note Some s...

Отзывы: