Winco DR20I4-/1 Series Скачать руководство пользователя страница 9

9

OPM-135/C

REMOTE START

The DSE7310 is able to start the generator when it receives 

a remote signal from any dry contact. This makes the system 

compatible with a wide range of control mechanisms 

including two-wire start automatic transfer switches. When 

the contact closes the controller will automatically start. 

When the contact is opened the generator will go through 

a cool-down cycle and turn off.  Connect the remote start 

leads to the Remote Start + and Remote Start - terminal 

blocks in the door behind the DSE 7310 controller. 

Depending on the distance, 14 to 16 gauge stranded wire 

should be used. It is suggested that these wires be labeled 

S1 and S23. 

Note: Any relay closure can be used to start and stop this 

generator. As long as the contact stays closed the engine 

generator set will continue to run. Once the relay is opened 

the unit will shut down and remain in the standby mode 

until the remote start relay is closed again.

E STOPS

In some applications additional emergency stops may be 

desired or necessary. The controller has terminals designed 

allowing the addition of multiple remote emergency stops. 

E-stops must be normally closed to work properly in this 

system. The e-stop circuit supplies power to fuel solenoid 

and the starter circuit. Opening any switch in the series 

prevents the engine from cranking or from receiving fuel to 

run. 

To wire additional emergency stop switches first remove 

the orange jumper between the two Emergency Stop 

terminal blocks. Failure to remove the jumper will prevent 

the remote switches from working properly. Add wires 

between the terminal block to the new switch(s). The 

switches must be wired in series for proper function. Test 

each e-stop after wiring to ensure they function properly.

SCR 

(DSENET)

4A 

(DSENET)

4B 

(DSENET)

Battery Charge Fail Emergency Stop Emergency Stop Remote S

tart +

Remote S

tart -

Ground Ground B Battery -

Two-Wire Start Hook-Ups

SCR 

(DSENET)

4A 

(DSENET)

4B 

(DSENET)

Battery Charge Fail Emergency Stop Emergency Stop Remote S

tart +

Remote S

tart -

Ground Ground B Battery -

E-Stops

SERIAL COMMUNICATION

DSE provides a series of remote accessories that can help 

provide useful information to operators. These accessories 

communicate over the DSE Net. Terminal blocks are wired 

to the distribution panel to aid in installation. Follow the 

instructions included with each accessory.

The generator controller can communicate with a variety 

of controls and monitoring systems, including RS232 and 

RS485. The ports are wired onto the back of the DSE7310. 

In order to finalize communication the program will need 

to be adjusted using the free DSE configuration software to 

enable the commutation. Contact Winco service for a list of 

register values.

INSTALLING THE BATTERY

CAUTION: 

In the following battery installation procedure, check to be 

sure the DSE7310 is in the “stop” position. This should be 

your last step before initial start-up.

A customer supplied Group 24/350 CCA battery is required 

to complete the installation. Installation of the highest CCA 

rated battery, within the correct BCI group, will increase 

cold weather starting performance.

BATTERY REQUIREMENTS

Model

Voltage

BCI Group

Min. CCA 
Rating

DR20I4

12

24

650

Installation and servicing of batteries must only be 

preformed or supervised by personnel knowledgeable of 

batteries and the required precautions. Keep unauthorized 

personnel away from batteries.

When installing or replacing batteries, use the proper 

group/size starting battery. The battery should be a 

maintenance-free lead acid design. Deep cycle batteries will 

not work for this application.

CAUTION: PERSONAL DANGER:

NEVER

 dispose a battery in a fire. The battery is capable of 

exploding.

DO NOT

 open or mutilate the battery. Released electrolyte 

is known to be harmful to the skin and eyes and to be very 

toxic.

These engine-generator sets are all NEGATIVE ground. Be 

very careful  not to connect the battery in reverse polarity, 

as this may short circuit the battery charging system on the 

engine.

CAUTION: 

A battery presents a risk of electrical shock and high short 

circuit current. The following precautions must be observed 

when working with batteries:

  1. Remove watches, rings, and other metal objects.

  2. Use tools with insulated handles.

  3. Check both the battery cable ends and the battery 

    posts to be sure they are free of corrosion.

  4. Always connect the battery positive cable first and then 

Содержание DR20I4-/1 Series

Страница 1: ...AL 1 DEG ANGULAR 9 15 2016 ZJF COPY YOUR MODEL AND SERIAL NUMBER HERE No other WINCO generator has the same serial number as yours If you should ever need to contact us on this unit it will help us to...

Страница 2: ...FILTER CLEANING RADIATOR CHANGING THE FUEL FILTER STORAGE MAINTENANCE SCHEDULE TROUBLESHOOTING TABLE 16 ENGINE HARNESS SCHEMATIC 17 WIRING SIZE TABLE 17 DSE7310 WIRING DIAGRAM 18 WIRING DIAGRAMS 19 LI...

Страница 3: ...k exhaust gas asphyxiation or fire Please read all safety instructions carefully before installation or use Keep these instructions handy for future reference Take special note and follow all warnings...

Страница 4: ...everal of the major components also have their own individual data plates providing additional information to document build data for warranty and replacements parts Be sure to have the main WINCO uni...

Страница 5: ...enerator for operation take a couple of minutes to ensure the unit you have received is the correct model and review the specification pages in this manual to ensure that this unit meets your job requ...

Страница 6: ...aller The factory weather enclosures are acoustical housing intended for outdoor installation only Factory weather enclosed units are not intended to be used indoors and no support is available to ass...

Страница 7: ...pipe to aid your installation Ensure proper alignment with the generator The flex can be eliminated if it is pushed to one side to make a connection The most direct path possible should be used to ge...

Страница 8: ...ert the wire into the larger circular hole B Remove the screwdriver to secure the wire into place A B A C ELECTRICAL CONNECTIONS NOTICE CLASS 1 WIRING METHODS ARE TO BE USED FOR ALL FIELD WIRING CONNE...

Страница 9: ...ries of remote accessories that can help provide useful information to operators These accessories communicate over the DSE Net Terminal blocks are wired to the distribution panel to aid in installati...

Страница 10: ...must be clean and tight Depending on your battery type check the electrolyte in the battery periodically to be sure it is above the plates Never allow the battery to remain in a discharged condition...

Страница 11: ...N PERSONAL INJURY Only check oil when the engine is not running and is at a low temperature in order to avoid the risk of burns 1 Remove the dipstick and ensure the oil level is between the Min and Ma...

Страница 12: ...AC On three phase panels the G2 voltage level should also be checked ON 240 VOLT DELTA SYSTEMS BE SURE YOU KNOW WHERE THE HIGH VOLTAGE WILD LEG IS IT MUST BE IN THE SAME LOCATION ON THE LINE SIDE AS I...

Страница 13: ...not connected to a battery charger A solar charger kit is the easiest way to always maintain the battery during storage in mobile applications The supplied battery charger can be plugged in to an exte...

Страница 14: ...O NOT dispose or allow oil to seep into the ground or sewer systems doing so will cause environmental damage CHANGING OIL FILTER The filter must be replaced when the lubricant oil is changed Only use...

Страница 15: ...iquid in accordance to local codes DO NOT dispose or allow liquid to seep into the ground or sewer systems doing so will cause environmental damage CLEANING RADIATOR The surfaces of the radiator come...

Страница 16: ...citer stator AC short in the output leads Defective open generator output breaker Wiring error protective liquid ISO 4113 and introduce the liquid by pressurizing the circuit and driving the engine fo...

Страница 17: ...418 431 458 480 519 550 572 585 50 68 86 100 118 137 155 177 205 237 264 291 319 346 391 432 473 487 505 532 560 605 642 669 683 8 6 4 3 2 1 1 0 2 0 3 0 4 0 250 300 350 400 500 600 700 750 800 900 100...

Страница 18: ...18 OPM 135 C DSE7310 WIRING DIAGRAM...

Страница 19: ...WIRING DELTA SINGLE PHASE 120 240 VOLTS SINGLE PHASE AC WIRING 4 LEAD WIRING DIAGRAMS 24 60708 165 THREE PHASE AC WIRING HIGH AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480...

Страница 20: ...omponent of the product that is no longer manufactured or available Additionally WINCO Inc will not be liable for any engine replacement that may require an emissions tier level change THERE ARE NO EX...

Отзывы: