Winco DR20I4-/1 Series Скачать руководство пользователя страница 13

13

OPM-135/C

NOTICE:

If for any reason during the check out procedure the 

voltage and frequency are not correct, depress the STOP/

RESET button and correct the trouble before proceeding.

4. Stopping - There are two ways to stop the unit when it is 

  in the manual mode. Pressing the STOP/RESET button will 

  stop the unit immediately. Pressing the AUTO mode 

  button will stop the unit but only after the cool down 

  timers have timed out and there is no remote start signal 

  being sent to the unit.

AUTO MODE

To activate the automatic start mode you will just need to 

depress the AUTO button, the LED indicator beside the 

button confirms that the unit is in automatic mode.

To test the Automatic Transfer Switch, follow the instruction 

on the operator’s manual that came with the transfer 

switch. If you get a fault during the initial start up or prior 

to start up, it is most likely a false warning light. Simply reset 

the ATS to start over.

Once you have completed testing of the ATS, be sure you 

ALWAYS leave the system in the standby mode,unless 

servicing the unit. For standby operation, press the AUTO 

button on the front of the control. The green light should 

light up next to the AUTO button.

NOTE: 

For setting the exerciser circuit, for all ATS, see the 

operator’s manual shipped with the ATS. 

CONTROL POWER

The DSE7310 controller consumes small amounts of battery 

power when it is in use. The controller comes with a power 

switch that disconnects battery power when it is not in use. 

The switch is designed with a safety relay that prevents it 

from removing power to the controller while the generator 

is operating. If the switch is turned off while the engine is 

running it will continue operating until the engine shuts 

down and then the controller will power down. 

This switch should be used when the generator is not 

going to be used over the course of several days and the 

generator is not connected to a battery charger. 

A solar charger kit is the easiest way to always maintain the 

battery during storage in mobile applications. The supplied 

battery charger can be plugged in to an extension cord on 

mobile applications.

OPERATING CONDITIONS

NORMAL OPERATION

This generator-engine set needs load and should not idle 

for long periods of time.

If the generator application is for emergency standby the 

generator should be exercised at least monthly ideally 

under load. Load banking the generator at least annually 

will help keep the engine in good condition. 

HARSH ENVIRONMENTS 

OPERATIONS

Some applications require the generator to operate in 

harsh environments. One of the most common hazards are 

extremely dusty conditions. In harsh conditions it is often 

necessary to take additional steps to keep the equipment 

clean and operating at its peak. Maintenance intervals on 

lubricant and filter changes may need to be shortened. An 

oil quality testing program can also provide early warnings 

or oil degradation. Efforts may need to be made to reduce 

the amount of dust and debris entering the housing and 

generator components. 

COLD WEATHER OPERATIONS

The minimum starting temperature with block heater is 

-13°F.

The degree of fluidity of the engine oil may be reduced at 

low temperatures due to the separation of the paraffin. This 

results in the filters becoming clogged.

Oil companies must respect these standards, which provide 

for the distribution of fuels adapted to the climatic and 

geographical conditions in various countries.

This generator-engine set needs load and should not idle 

for long periods of time.

If the generator set will be run in extremely cold 

environments it may be beneficial to provide means to 

reduce air circulation to increase the temperature of the 

enclosure. 

Inspect the hoses regularly during cold operation looking 

for signs of freezing. If the line freezes it will cause pressure 

to build in the crankcase and may cause an engine seal 

failure. If the engine operates below optimal temperatures 

for long periods of time damage may occur.

Содержание DR20I4-/1 Series

Страница 1: ...AL 1 DEG ANGULAR 9 15 2016 ZJF COPY YOUR MODEL AND SERIAL NUMBER HERE No other WINCO generator has the same serial number as yours If you should ever need to contact us on this unit it will help us to...

Страница 2: ...FILTER CLEANING RADIATOR CHANGING THE FUEL FILTER STORAGE MAINTENANCE SCHEDULE TROUBLESHOOTING TABLE 16 ENGINE HARNESS SCHEMATIC 17 WIRING SIZE TABLE 17 DSE7310 WIRING DIAGRAM 18 WIRING DIAGRAMS 19 LI...

Страница 3: ...k exhaust gas asphyxiation or fire Please read all safety instructions carefully before installation or use Keep these instructions handy for future reference Take special note and follow all warnings...

Страница 4: ...everal of the major components also have their own individual data plates providing additional information to document build data for warranty and replacements parts Be sure to have the main WINCO uni...

Страница 5: ...enerator for operation take a couple of minutes to ensure the unit you have received is the correct model and review the specification pages in this manual to ensure that this unit meets your job requ...

Страница 6: ...aller The factory weather enclosures are acoustical housing intended for outdoor installation only Factory weather enclosed units are not intended to be used indoors and no support is available to ass...

Страница 7: ...pipe to aid your installation Ensure proper alignment with the generator The flex can be eliminated if it is pushed to one side to make a connection The most direct path possible should be used to ge...

Страница 8: ...ert the wire into the larger circular hole B Remove the screwdriver to secure the wire into place A B A C ELECTRICAL CONNECTIONS NOTICE CLASS 1 WIRING METHODS ARE TO BE USED FOR ALL FIELD WIRING CONNE...

Страница 9: ...ries of remote accessories that can help provide useful information to operators These accessories communicate over the DSE Net Terminal blocks are wired to the distribution panel to aid in installati...

Страница 10: ...must be clean and tight Depending on your battery type check the electrolyte in the battery periodically to be sure it is above the plates Never allow the battery to remain in a discharged condition...

Страница 11: ...N PERSONAL INJURY Only check oil when the engine is not running and is at a low temperature in order to avoid the risk of burns 1 Remove the dipstick and ensure the oil level is between the Min and Ma...

Страница 12: ...AC On three phase panels the G2 voltage level should also be checked ON 240 VOLT DELTA SYSTEMS BE SURE YOU KNOW WHERE THE HIGH VOLTAGE WILD LEG IS IT MUST BE IN THE SAME LOCATION ON THE LINE SIDE AS I...

Страница 13: ...not connected to a battery charger A solar charger kit is the easiest way to always maintain the battery during storage in mobile applications The supplied battery charger can be plugged in to an exte...

Страница 14: ...O NOT dispose or allow oil to seep into the ground or sewer systems doing so will cause environmental damage CHANGING OIL FILTER The filter must be replaced when the lubricant oil is changed Only use...

Страница 15: ...iquid in accordance to local codes DO NOT dispose or allow liquid to seep into the ground or sewer systems doing so will cause environmental damage CLEANING RADIATOR The surfaces of the radiator come...

Страница 16: ...citer stator AC short in the output leads Defective open generator output breaker Wiring error protective liquid ISO 4113 and introduce the liquid by pressurizing the circuit and driving the engine fo...

Страница 17: ...418 431 458 480 519 550 572 585 50 68 86 100 118 137 155 177 205 237 264 291 319 346 391 432 473 487 505 532 560 605 642 669 683 8 6 4 3 2 1 1 0 2 0 3 0 4 0 250 300 350 400 500 600 700 750 800 900 100...

Страница 18: ...18 OPM 135 C DSE7310 WIRING DIAGRAM...

Страница 19: ...WIRING DELTA SINGLE PHASE 120 240 VOLTS SINGLE PHASE AC WIRING 4 LEAD WIRING DIAGRAMS 24 60708 165 THREE PHASE AC WIRING HIGH AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480...

Страница 20: ...omponent of the product that is no longer manufactured or available Additionally WINCO Inc will not be liable for any engine replacement that may require an emissions tier level change THERE ARE NO EX...

Отзывы: