Shower control
SanTec PROOF S6
31
EN
PROOF S6
Stagnation rinse:
DIP switch 6
Description of the functions
Serves to rinse water supply lines in order to remove stagnant water that
accumulates during longer periods of disuse.
DIP switch 6 ON = Stagnation rinse enabled.
DIP switch 6 OFF = Stagnation rinse function disabled (default setting).
Time interval
Can be set from 3–48 h at the
interval control (see p. 21).
Automatic stagnation rinse
If the fitting has not been used
for the set period, the stagnati-
on rinse operation is automati-
cally executed for 10 s.
Safety
If you are in the sensor range
or if the cleaning stop function
is enabled, the stagnation rin-
se function will not start until
2 min after it has been
disabled.
3
-
48
h
10
s
1 2 3 4 5 6
ON
OFF