Shower control
SanTec PROOF S6
21
EN
PROOF S6
Configuring the programs & functions
Einstellregler:
D.
Range control
to detect user interaction
Sensor range preset to 70 cm
(configurable from 30 to
70 cm).
Sets the infrared sensor range
from 30–70 cm.
Automatic range adjustment
within the preset maximum
range.
E.
Time control
set to safety flow arrest after
10 min (configurable from
10 s to 10 min).
self-closing program mode:
10 s to 60 s.
After the configured maximum
flow time has elapsed, the
water stops automatically to
prevent unintentional conti-
nuous activation.
F.
Interval control
for stagnation rinse
preset to 48 h
(configurable from 3 to 48 h).
If the fitting has not been
used for the set period, the
device will automatically
perform a 10-s rinse to flush
stagnant water from the
pipes.
Program activation – DIP switches 1 and 2:
Program
DIP switch 1
DIP switch 2
Description
Semi automatic mode
1)
OFF
ON
Page 26
Fully automatic mode
ON
ON
Page 27
Manual mode
OFF
OFF
Page 28
DIP switches:
1)
Preset program.
2)
Only for models with thermal disinfection:
Function activation – DIP switches 3–6:
DIP switch
Function
Factory setting
Description
3
Shut-off delay ON = 5 s / OFF = 2 s
OFF
4
Warm water rinse
ON
Page 29
5
Protection from scalding
2)
ON
Page 30
6
Stagnation rinse
OFF
Page 31