25
Installation and operating instructions Tagus Vac 7-30
English
7.5 Error messages
A
Necessary, reset possible within normal use
(control restarts after resetting).
B
No duty, automatic reset within normal use.
Nr
Message
Description
Reset Possible cause
Troubleshooting
1
Pressure too low
System pressure too
low, is outside working
pressure range
B
• Leakage
• Pressure-holding value wrongly set
• Wrong admission pressure
• Filling pressure too low
• Eliminate leakage
• Set correct pressure-holding value
• Increase filling pressure up to working
pressure range
2
Pressure too
high
System pressure too
high, is outside working
pressure range
B
• Pump does not switch off
• Diaphragm expansion vessel too small/
wrong admission pressure
• Filling pressure too high
• Check control
• Check admission pressure / use larger
diaphragm expansion vessel
• Lower filling pressure to working
pressure range
3
Entrycap. too
low
Litres counter does not
supply water after
make-up request
A
• No pulses sent from litres counter,
because:
• litres counter defective
• cable not connected
• setting value too low for litres counter
response time
• Replace litres counter
• Connect cable
• Use higher setting value for response
time
5
Cycle interval
Make-up cycle interval
too short
A
• Leakage in system
• False setting value
• Eliminate leakage
6
Nr. of cycles
Maximum number of
cycles within time
window exceeded
A
• Leakage in system
• False setting value
• Eliminate leakage
• Program correct settings
7
Fill error
Filling without request
(litres counter sends
signal without filling)
A
• Leakage
• Solenoid valve don‘t close/defective
• Eliminate leakage
• Replace solenoid valve
8
Quantity limit
Maximum quantity in a
make-up cycle exceeded
A
• Leakage
• Setting value for flow rate reduction
too low
• Eliminate leakage
• Correct the setting value
9
Runtime
protection
Maximum time of
make-up cycle exceeded
A
• Leakage
• Setting value for flow rate reduction
too low
• Pump doesn‘t deliver
• Eliminate leakage
• Correct the setting value
• Deaerate pump
10
Exchange
module
Softening module
exhausted
A
• Module capacity (water treatment)
exhausted
• Replace module
11
Low mA
P-sensor
Interruption of current
loop of pressure
sensor
A
• Sensor defective
• Terminal/cable defective
• Replace sensor
• Check/exchange terminal/ cabling
12
High mA
P-sensor
Short-circuit in current
loop of pressure sensor
A
• Sensor defective
• Terminal/cable defective
• Short circuit
• Replace sensor
• Check/exchange terminal/ cabling
13
Vacuum error
3 times in succession
insufficient vacuum for
dearation
A
• Temperature in return branch higher
than 70 °C
• Pump does not operate continuously
• Leakage in Tagus Vac 7-30
• Vent. device doesn‘t close
• Take steps for ensuring return
temperatures below 70°C!
• Replace pump
• Locate leakage in Tagus Vac 7-30
• Clean or replace vent. Device
14
Level switch
error
Low level
B
• Vent. device defective
• Strainer / inlet protected
• Valves closed
• Clean or replace vent. Device
• Clean strainer
• Open valves
Содержание Tagus Vac
Страница 2: ......
Страница 4: ......
Страница 30: ......
Страница 56: ......
Страница 82: ......
Страница 108: ......
Страница 134: ......
Страница 160: ......
Страница 186: ......
Страница 188: ...208 WILO 07 2018 1 1 1 1 2 1 3 Wilo 1 4 2 2 1 2 2 Wilo Wilo 2 3...
Страница 189: ...209 Tagus Vac 7 30 2 4 DIN EN 12828 2 5 2 5 1 1 1 2 5 2 2 6 A Tagus Vac B C D Tagus Vac XX 8 bar 70 oC A C B D...
Страница 191: ...211 Tagus Vac 7 30 12 14 13 8 9 16 15 ENA 30 Tagus Vac 30 8 9 Rp3 4 15 2 16 2...
Страница 193: ...213 Tagus Vac 7 30 4 4 1 9 4 2 6 2 18 00 08 00 3 3 2 P Po 0 2 bar 0 1 bar D 6 1 6 1 Po P Static P Steam...
Страница 194: ...214 WILO 07 2018 5 5 1 9 5 2 0 5 m 0 5 m 0 5 m 80 0 C 40 C Tagus Vac 7 45 C Tagus Vac 10 30 5 3 0 2 mm DN 20...
Страница 195: ...215 Tagus Vac 7 30 Tagus Vac 7 30 Tagus Vac 7 30 5 4 SCU...
Страница 197: ...217 Tagus Vac 7 30 6 6 1 6 2 Ku1 Ku2 FL1 FL2 A A 10 10 11 12 1 turbo P Ku1 Ku2 FL1 FL2 A A 10 10 11 12 1 turbo P...
Страница 200: ...220 WILO 07 2018 7 70 C 7 1 7 2 7 3 Tagus Vac 7 30 7 4 water treatment...
Страница 201: ...221 Tagus Vac 7 30 7 5 A B 1 B 2 B 3 A 5 A 6 A 7 A 8 A 9 A 10 A 11 mA P A 12 mA P A...
Страница 203: ...223 Tagus Vac 7 30 8 OFF OFF 2 1 230 V 2 230 V...
Страница 209: ...229 Tagus Vac 7 30 150 20 2 5 0 3 480 ON 00 03 OFF 00 10 0 800 365 0 0 bar 10 0 bar 480 50 5...
Страница 210: ...230 WILO 07 2018 12 3 Start Maintenance done 250 200 000001...